Chapter 5 Function Parameter Detail SVF-MN Series Frequency Inverter Operation Manual
83
P02
Halt mode
0
~
1
0
0
:
Dec to stop
When the drive stops, it would slow down step by step According to
the set Dec. time, it would stop until the output freq. to be zero.
1
:
Coast to stop
When the stop command is valid, the drive would stop output
immediately and block output signal, the motor would run freely and
stop.
P03
Max output frequency
50.00
~
400.0Hz 50.00
Set the max output frequency of the drive, it is the basis of freq. set
and Acc. and Dec. speed.
P04
Motor rated
freq.
10.00
~
P03 50.00
P05
Motor rated
voltage
220V: 0.1
~
250.0V
380V: 0.1
~
400.0V
220.0
380.0
This parameter should be set According to the rated frequency and
rated voltage on the motor nameplate.
P06 Intermediate
frequency
P08
~
P04 10.00
P07 Intermediate
voltage
220V: P03
~
P05
380V: P03
~
P05
44.0
76.0