Chapter 7 Troubleshooting SVF-MN Series Frequency Inverter Operation Manual
154
Fault
code
Fault
categories
Possible reasons
of fault
Actions
Vent is
obstructed or fan
does not work
Clean the vent or
replace the fan
Over-temperature
Lower the ambient
temperature
Wires or
connectors of
control board are
loose
Check and rewiring
Auxiliary power
supply is
damaged or
IGBT driving
voltage is too
low
Seek service
Short-circuit of
IGBT bridge
Seek service
E016
IGBT
module’s
heatsink
overheat
Control board is
abnormal
Seek service
E017
External
equipment
fails
Terminal SI used
for inputting
external faults
acts
Check the input of
the external device
E018