SVF-MN Series Frequency Inverter Operation Manual Chapter 5 Function Parameter Detail
92
When P38 isn’t set to 02, the original settings function is set by P39
come back.
P39
Multi-function input
terminal S2 function
selection(when P38 is 2, S2
is fixed as run control
terminal)
5
P40
Multi-function input
terminal S3 function
selection
6
P41
Multi-function input
terminal S4 function
selection
7
P42
Multi-function input
terminal S5 function
selection
00
~
28
8
Parameter P39
~
P42 function list
Set
value
Function
Description
00
No
function
This terminal is without any function.
01
Coast to
stop
control
If close the terminal corresponding with this
parameter, the drive would block output, the
motor would coast to stop, when this terminal
is disconnected, the drive would start
According to rotate speed track restart mode.