Fault code Fault
Possible cause
Correcting measures
10
Input line
supervision
Input line phase is missing.
Check supply voltage and cable.
11
Output phase
supervision
Current measurement has detected
that there is no current in one motor
phase.
Check motor cable and motor.
12
Brake chopper
supervision
•
no brake resistor installed
•
brake resistor is broken
•
brake chopper failure
Check brake resistor. If the resistor is
ok, the chopper is faulty. Contact the
distributor near to you.
13
Frequency
converter under
temperature
Heatsink temperature is under -10
°C/-50 °F
14
Frequency
converter over
temperature
Heatsink temperature is over 90 °C/
194 °F. Over temperature warning is
issued when the heatsink
temperature exceeds 85 °C/185 °F.
Check the correct amount and flow of
cooling air. Check the heatsink for
dust. Check the ambient temperature.
Make sure that the switching
frequency is not too high in relation to
ambient temperature and motor load.
15
Motor stalled
Motor stall protection has tripped.
Check motor.
16
Motor
overtemperature
Motor overheating has been detected
by frequency converter motor
temperature model. Motor is
overloaded.
Decrease the motor load. If no motor
overload exists, check the
temperature model parameters.
17
Motor underload
Motor underload protection has
tripped.
Decrease the motor load. If no motor
overload exists, check the
temperature model parameters.
22
23
EEPROM
checksum fault
Parameter save fault
•
faulty operation
•
component failure
24
Changed data
warning
Changes may have occurred in the
different counter data due to mains
interruption
No special actions required. Take a
critical attitude to the counter data.
25
Microprocessor
watchdog fault
•
faulty operation
•
component failure
Reset the fault and restart. Should the
fault re-occur, contact the distributor
near to you.
32
Fan cooling
Cooling fan of the frequency
converter does not start, when ON
command is given
Contact the distributor near to you.
36
Control unit
NXS Control Unit can not control NXP
Power Unit and vice versa
Change control unit
37
Device change
Option board changed. Different
power rating of drive.
Reset
38
Device added
Option board added. Drive of different
power rating added.
Reset
39
Device removed
Option board removed. Drive
removed.
Reset
40
Device unknown
Unknown option board or drive.
41
IGBT temperature IGBT Inverter Bridge over
temperature protection has detected
too high a short term overload current
Check loading. Check motor size.
Instruction book
2920 1804 00
81
Summary of Contents for CPF 175
Page 1: ...CPF 175 CPVS 175 Instruction book ...
Page 2: ......
Page 7: ...11 Declaration of conformity 148 Instruction book 2920 1804 00 5 ...
Page 18: ...Flow diagram water cooled compressor with modulating control Instruction book 16 2920 1804 00 ...
Page 33: ...Menu structure for fixed speed compressors Instruction book 2920 1804 00 31 ...
Page 34: ...Menu structure for variable speed compressors Instruction book 32 2920 1804 00 ...
Page 60: ...Fixed speed compressors Instruction book 58 2920 1804 00 ...
Page 72: ...Fixed speed compressors Instruction book 70 2920 1804 00 ...
Page 104: ...Electrical connections for IEC variable speed compressors Instruction book 102 2920 1804 00 ...
Page 105: ...Electrical connections for CSA UL fixed speed compressors Instruction book 2920 1804 00 103 ...
Page 151: ......
Page 152: ...No 2920 1804 00 2012 08 ...