SpaceKeeper Cons ole (SKC) – Ins tallation Operation Maintenance Manual

10

OPERATION

condition can be obs erved on the thermos tat connection LEDs . (Note: A heat

pump thermos tat may caus e this s cenario).

2. Revers e Cycle Call – Poorly located automatic changeover thermos tats (ie.

thermos tats mounted on a wall oppos ite a dis charge grill, or a thermos tat in a

doorway to outs ide) can trigger heating and cooling mode changes many times

an hour. The CGC controller has a 10-minute anti-mode change timer when

changing from cooling to heating operation. The controller will not accept a

change in mode until 10 minutes have elaps ed s ince termination of the

oppos ite call.

Thermostat Connections

The CGC control board has been des igned to operate with mos t standard 24V AC

thermos tats . Thes e thermos tats are powered directly from the CGC board and provide

s ignals to the appropriate terminals depending on the operation at hand - Heat (W),

Cool (Y), Fan (G) or Aux (A). While most present-day thermos tats are compatible withthe

CGC control board, there are others that may not work properly. The following shouldbe

checked for s atisfactory performance prior to ins tallation:

1. Heat Pump Thermos tat – Some heat pump units do not have heat relays

(therefore are not compatible with s tandard thermos tats) and require “Heat

Pump Thermos tats ”. Thes e thermos tats call for both heating and cooling on

one of the s ignal wires . Thes e thermos tats are completely incompatible with

CGC’s controller.

2. Mercury bulb thermos tat - This type is problematic but can be us ed.

Unfortunately, the anticipators are a problem. Heat anticipators mus t be in

s eries with a high current relay or valve to function, s o do not perform on an

electronic circuit. This will res ult in larger than normal temperature s wings .

The cool anticipator, if overs ized, can bleed enough current to indicate a

cooling call even after it has been terminated.

3. Battery powered thermos tats – Thes e thermos tats were developed as

replacements for old mercury bulb thermos tats that had 4 wire connections

while 24V electronic thermos tats required 5 wires. Thes e will work with a CGC

board, although CGC does not recommend them. They require periodic battery

replacement, which is something that s hould be avoided if poss ible.

4. Power s tealing thermostats – This type of thermostat is electronic and was

als o developed as a replacement for old mercury bulb thermos tats . Thes e too

are problematic in that they bleed a small amount of current down the s ignal

wires and this may be interpreted as a s ignal for heat or cool.

5. Triac s witched controllers – This is a commonly used s witching device and all

controllers tes ted to date have functioned flawless ly. CGC recommends that

Summary of Contents for SKC-008

Page 1: ...Installation Operation Maintenance SpaceKeeper Console Hybrid Heat Pump SpaceKeeper Console SKC Models SKC 008 015 REV 02...

Page 2: ...6 CoolStart Up 7 CoolOperation 7 OperationalAlgorithm 9 ThermostatConnections 10 Shutdown Output 10 Fault AlarmOutput 11 4 COMMISSION START UP 12 5 MAINTENANCE 14 SKC 008 SKC 015 Wiring Diagram 16 6 A...

Page 3: ...ons of extreme temperature or humidity Subjecting the unit to conditions of this nature may result in significantly reduced performance reliability and operational life The unit is intended for interi...

Page 4: ...175 Unit Dimensions Model No Unit Dimensions inches L x W x H Water Connections Inlet Outlet inches Filter Dimensions inches L x W x H SKC 015 48 0 x 12 0 x 25 3 FPT 29 5 x 1 0 x 12 0 SKC 012 48 0 x...

Page 5: ...llation Procedure 1 This heat pump unit is to be installed within an indoor environment Locate the unit in an area where the surrounding air temperature is above 45 F 7 C at all times Do not attempt t...

Page 6: ...to the building s supply return and condensate piping should at this point be accessible through the bottom of the heat pump unit Using the swivel connectors re connect the supply and return hoses to...

Page 7: ...ed equipment located within the building mechanical room is configured to automatically provide each heat pump with water at the appropriate temperature Board Description The unit s electronic circuit...

Page 8: ...rant Temperature Tw Outgoing Water Temperature Co Condensate Level Ta Tr And Tw are 10k Ohm NTP thermistors while Co is a 100 Ohm NTP thermistor These inputs do not have LED indicators Fan 1 A fan cal...

Page 9: ...me situations particularlywhen the unit is cold the pressure switch will open during start up If the switch does not close within the 5 minute ignore period the compressor will immediatelybe turned of...

Page 10: ...be set to alarm however if the open switch closes within 10 minutes a restart cycle is initiated The restart cycle begins with a 10 minute delay after which if there is a cool call in place and all o...

Page 11: ...el rises above the sensor it will not warm up during the heating cycle and the temperature change will be insignificant It is this lack of temperature change that the controller sees as an impending c...

Page 12: ...le with standard thermostats and require Heat Pump Thermostats These thermostats call for both heating and cooling on one of the signal wires These thermostats are completely incompatible with CGC s c...

Page 13: ...an be initiated individually with on board 24V power This capability allows unit or compressor shutdown based on a door switch a light switch or occupancyswitch A separate 24V power supply is required...

Page 14: ...en all isolation valves to the unit With the unit in operation ensure that the entering and leaving fluid temperatures are acceptable There is typically an 8 to 12 degree drop or rise in temperature d...

Page 15: ...lean Unit Filter Confirm that the unit filter that is being used is clean A clean filter contributes to the proper operation of the unit byensuring that there is adequate air flow across the coil Fan...

Page 16: ...an Motors Annually All CGC Hybrid Heat Pumps are permanentlylubricated when shipped from the factory Do not oil or lubricate the fan motors Visual Inspection Visually inspect units and give special at...

Page 17: ...check the unit for a dirty air filter abnormal entering leaving water temperature inadequate water flow or internal malfunctions that may be causing high or low pressure conditions If the unit contin...

Page 18: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 16 MAINTENANCE STANDARD WIRING DIAGRAM...

Page 19: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 17 DETAILS SpaceKeeper Console Dimensional Diagram Complete Unit SpaceKeeper Console Dimensional Diagram Chassis...

Page 20: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 18 DETAILS Dimensional Diagram Piping andReceptacle Plate Note The fresh air damper mechanism is optional...

Page 21: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 19 DETAILS SpaceKeeper Console Hose Assembly Connection...

Page 22: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 20 DETAILS SpaceKeeper Console Hose Assembly Connection...

Page 23: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 21 DETAILS SpaceKeeper Console Hose Assembly Connection...

Page 24: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 22 DETAILS...

Reviews: