Product safety
The UPS connection procedures and operational instructions described within
this manual must be followed in the indicated order.
An additional circuit breaker with breaking capacity 6kA shall be used between
power source and input when installation this unit
CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided
with branch circuit overcurrent protection for :
63A rating, for 6kVA models,
100A rating, for 10kVA models
The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible.
The unit can be disconnected from AC power source by opening this circuit
breaker.
An additional AC contactor is used for back feed protection and must comply with
IEC/EN 62040-1 (the creep age and clearance distances shall meet the basic
insulation requirements for pollution degree 2).
Disconnection and overcurrent protection devices shall be provided by others for
permanently connected AC input (Normal AC/Bypass AC) and AC output circuits.
Check that the indications on the rating plate correspond to your AC powered
system and to the actual electrical consumption of all the equipment to be
connected to the system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the
equipment and shall be easily accessible
Never install the system near potential liquid hazards or in an excessively
damp/humid environment.
Never let foreign objects enter the UPS system.
Do not house within and enclosed space to ensure adequate ventilation and
proper heat dissipation
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25ºC to +60ºC with battery (-15ºC
to +40ºC without battery).