40
Parallel cable loss
Fault (Red) LED is On.
Beep continuous.
Code: F0E2
In parallel configurations a
parallel cable disconnect
Reconnect the parallel
cable to clear the fault. If
issue persists contact your
service representative
Parallel system battery
status
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E6
In parallel configurations a
UPS is reporting a fault with
batteries/EBM.
Check battery connections
Line input different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E7
Within parallel system
,
UPS1
inout ok
,
UPS2 input lost
Check the line input
Power strategy different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E9
Parallel system
,
UPS mode
not consistent through
configuration i.e. normal
,
converter
,
HE are different
Check UPS OP mode, set
OP mode be the same
Rated power difference
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EA
Power rating between
individual ups in parallel are
different
Ensure all power ratings
within the parallel are the
same
HE in parallel
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EB
Within parallel systems one
or more UPS modes are set as
HE
HE not allow in parallel
configurations
8.2 Silencing the alarm
Press the ESC (Escape) button on the front panel display for 2 Seconds to silence
the alarm. Check the alarm condition and perform the applicable action to resolve
the condition. If an alarm status changes the alarm will need to be silenced again.