INSTALLING THE EVAPORATOR UNIT
9.
Remove the protective caps from the liquid and
suction line connection tubes (as shown above ).
10.
Using copper tubing per line set sizing chart, route
the liquid and suction lines to the tubing coming from
the unit.
11.
Place a wet rag around the suction and liquid lines
approximately 4” from the braze joints. This will
prevent excess heat from damaging components.
12.
To prevent oxidation, purge the system with nitrogen.
13.
Braze the copper tubing to the connections on the
evaporator unit.
BRAZE LINE SET USING
COUPLING
14.
Insulate the suction line using Armaflex or similar
insulation.
15.
Route the drain line out of the evaporator unit with
the line set. Connect using the supplied 1/4” barb
coupling.
16.
Route the power wire, bottle probe, and display
cable into the unit.
17.
Slide the electrical panel up and out of the unit.