www.cellarcool.com | Page 45
CM2500
TROUBLESHOOTING GUIDE
Unit has ice forming on the evaporator unit (fan coil unit)
Possible cause
Solution
Evaporator filter or coil is dirty
Remove the filter and wash it, then clean the coil with a vacuum.
If coil is very dirty, use a spray bottle with a small amount of liquid
dish detergent or coil cleaner. Spray coil, let set for five minutes, then
flush with fresh water.
There is something blocking the supply and/or return air
Remove blockage
The evaporator fan is not turning on
Call a service tech to troubleshoot
The evaporator unit (fan coil unit) has not gone through an Anti-
Frost Cycle yet
Check the coil for surface ice. Melt with blow drier until coil is warm
to the touch. Soak up water with a towel.
If evaporator unit (fan coil unit) continues to ice
Observe ice formation pattern. If only part way up the coil face, the
system could be low on refrigerant. If all the way up, the coil may be
dirty or airflow is blocked.
Unit does not run/power up
Possible cause
Solution
Unit is not draining properly
1. Check to see that the unit is level; if not, level it
2. Verify that the drain line is not clogged; if so, clear obstruction
3. Ensure that the condensate pump is operating
Evaporator unit (fan coil unit) is not plugged in
Make sure the unit is plugged into an outlet
Power switch not on
Turn unit on by pressing the power button on the control
Line voltage rating is incorrect for the system
Check line voltage to make sure there is 110V-120V
Bottle at set point
Lower set point
Thermostat not calling for cooling
Lower set point
Faulty thermostat or wiring
Call Customer Service at 1-800-343-9463
Cellar temperature is too warm
Possible cause
Solution
The temperature of the room to which the condensing unit exhausts
exceeds 110°F
Intake temperature needs to drop below 110°F
The system is undersized for the cellar
Order correct size system
There is something blocking the supply and/or return air on the
evaporator unit (fan coil unit) or the condensing unit
Remove air flow obstruction
Evaporator unit (fan coil unit) is mounted too low in the cellar
Relocate unit so the distance from the ceiling and top of the unit is
no more than 18”
One or more of the fans is not turning on
Please contact the installing technician to troubleshoot
Compressor is not turning on
Please contact the installing technician to troubleshoot
Compressor keeps cycling on overload
Make sure all fans are working and there is no airflow obstruction
Poor seal around door or other areas requiring a seal (around the
unit, wall joints, etc.)
Make sure there are no air gaps around the door. If door seal is
damaged, replace it.
Set point too high
Lower the set point
Evaporator coil is frosted or iced up
Observe ice formation pattern. If only part way up the coil face,
evaporator unit (fan coil unit) could be low on refrigerant. If so, con-
tact your installing technician to assist with troubleshooting.
System runs constantly
Possible cause
Solution
Leaky door seal or poorly insulated cellar
Fix leaky door seal and insulate cellar in accordance with this manual