BYPASS TEST PROCEDURE
1.
Disconnect power from the evaporator unit.
2.
Loosen the two (2) screws on the front of the grille or duct plenum.
3.
Pull the grille or duct plenum away from the evaporator unit.
4.
Remove the screw securing the control panel in place.
5.
Slide the control panel down, out of the evaporator housing. The control panel has two (2) hooks which allow it to attach to
the evaporator unit for easy serviceability.
6.
Disconnect the Molex connector labeled #4.
7.
Locate the bypass plug included in the accessory kit.
8.
Plug the bypass plug into the male Molex connector.
9.
Connect power to the evaporator unit. The unit should immediately turn on. If all the components are not operational,
disconnect power immediately and contact customer service. If all components seem to be operating correctly, allow the unit
to run for four (4) hours. Monitor the temperature of the cellar to determine if the unit is cooling properly.
10.
Once the test is complete, remove the bypass plug. Plug the Molex connector back in to the unit’s wiring.
11.
Replace the control and faceplate.
NOTE: If instructed by a CellarCool representative, follow the directions below to test the cooling unit using the bypass plug
provided in the accessory kit.