![Ceiec Electric PMC-630 E User Manual Download Page 62](http://html1.mh-extra.com/html/ceiec-electric/pmc-630-e/pmc-630-e_user-manual_2579014062.webp)
62
Ceiec Electric Technology
+8
RW
Trigger 1
2
UINT16
0 to 21 (Default=1)
+9
RW
Trigger 2
2
UINT16
0 to 21 (Default=2)
* Default
Table 5-16 Setpoint Setup Register Structure
Notes:
1)
“
Parameter
” specifies the parameter to be monitored. Table 5-17 below provides a list of
Setpoint Parameters.
Key
Parameter
Scale/Unit
1
VLN
x100, V
2
VLL
x100, V
3
I
x1000, A
4
I4
x1000, A
5
Freq
x100, Hz
6
∑kW
kW
7
∑kvar
kvar
8
P.F.
x1000
9
DI1
1)
For Over Setpoint, the Active Limit is DI Close
(
DI=1
), and Inactive Limit is DI Open (
DI=0
);
2)
For Under Setpoint, the Active Limit is DI Open
(
DI=0
), and Inactive Limit is DI Close (
DI=1
);
10
DI2
11
DI3
12
DI4
13
DI5
14
DI6
15
Reserved
/
16
∑kW Demand
kW
17
∑kvar Demand
kvar
18
P.F. Demand
x1000
19
V THD
x10000
20
V TOHD
x10000
21
V TEHD
x10000
22
I THD
x10000
23
I TOHD
x10000
22
I TEHD
x10000
25
Voltage Unbalance
x1000
26
Current Unbalance
x1000
Table 5-17 Setpoint Parameters
2)
“
Trigger
” specifies what action the setpoint will take when it becomes active. Table 5-18
below provides a list of Setpoint Triggers.
Key
Action
Key
Action
0
None
11
DR #8
1
RO1
12
DR #9
2
RO2
13
DR #10