53
Ceiec Electric Technology
1612
RO
Vca min
INT32
x100, V
1614
RO
VLL average min
INT32
x100, V
1616
RO
Ia min
INT32
x1000, A
1618
RO
Ib min
INT32
x1000, A
1620
RO
Ic min
INT32
x1000, A
1622
RO
I average min
INT32
x1000, A
1624
RO
I4 min
1
INT32
x1000, A
1626
RO
kWa min
INT32
W
1628
RO
kWb min
INT32
W
1630
RO
kWc min
INT32
W
1632
RO
∑kW min
INT32
W
1634
RO
kvara min
INT32
var
1636
RO
kvarb min
INT32
var
1638
RO
kvarc min
INT32
var
1640
RO
∑kvar min
INT32
var
1642
RO
kVAa min
INT32
VA
1644
RO
kVAb min
INT32
VA
1646
RO
kVAc min
INT32
VA
1648
RO
∑kVA min
INT32
VA
1650
RO
P.F.a min
INT32
x1000
1652
RO
P.F.b min
INT32
x1000
1654
RO
P.F.c min
INT32
x1000
1656
RO
∑P.F. min
INT32
x1000
1658
RO
FREQ min
INT32
x100, Hz
1660
RO
V Unbalance min
INT32
x1000
1662
RO
I Unbalance min
INT32
x1000
1664
RO
Va THD min
INT32
x10000
1666
RO
Vb THD min
INT32
x10000
1668
RO
Vc THD min
INT32
x10000
1670
RO
Ia THD min
INT32
x10000
1672
RO
Ib THD min
INT32
x10000
1674
RO
Ic THD min
INT32
x10000
Table 5-7 Max/Min Value per Demand Period
Note:
1)
Registers 1424 and 1624 are valid only if the device is equipped with the I4 Current Input.
Otherwise, they are reserved.
5.1.7 Peak Demand Log
The Current Peak Demand data is 1000 times the actual value. For example, if the register 1818
contains a value of 5005, the actual kW Peak Demand value is 5.005A.
Register
Property
Description
Format
Scale/Unit
1800-1805
RO
∑kW Peak Demand of This Month
See
Section 5.11.1
Peak Demand
Data Structure
W
1806-1811
RO
∑kvar Peak Demand of This Month
var
1812-1817
RO
∑kVA Peak Demand of This Month
VA
1818-1823
RO
Ia Peak Demand of This Month
x1000, A