3.2.3 Front Panel Setup Parameters
The Setup Configuration mode provides access to the following setup parameters:
Label
Parameters
Description
Options/Range
Default
menu
1
st
level
2
nd
level
PROGRAMMING
Setup Configuration
mode
/
/
PASWORD
Password
Enter Password
/
“0”
PAS SET
Change Password
YES/NO
NO
New PAS
New Password
Change Password
0000 to 9999
“0”
SYS SET
Configure System
Parameters
YES/NO
NO
TYPE
Wiring Mode
The Wiring
Connection of the
meter
WYE/DELTA/DEMO
WYE
PT
PT Ratio
1
PT Ratio
1 to 10,000
1
CT
CT Ratio
1
CT Ratio
1 to 30,000 (1A)
1 to 6,000 (5A)
1
I4
I4 Ratio
I4 Ratio
1 to 10,000
1
PF SET
P.F.
Convention
2
P.F. Convention
IEC/IEEE/-IEEE
IEC
KVA SET
kVA
Calculation
3
kVA Calculation
Method
V/S
V
HD SET
Harmonics
Calculation
4
Harmonics
Distortion
Calculation Method
FUND/RMS
FUND
V NOM
VLL Nominal
Secondary
Voltage
(VLL
nominal
)
VLL Nominal Voltage
of Secondary Side
100 to 700 (V)
100
Hz NOM
Nominal
Frequency
(f
nominal
)
Nominal Frequency
50/60
50
I1 REV
Phase A CT
Reverse Phase A CT
Polarity
YES/NO
NO
I2 REV
Phase B CT
Reverse Phase B CT
Polarity
YES/NO
NO
I3 REV
Phase C CT
Reverse Phase C CT
Polarity
YES/NO
NO
BLTO SET
Backlight
Time-Out
5
Set Backlight
Time-out
0 to 60 (mins)
3
COM1 SET
Configure COM1
YES/NO
NO