![Ceiec Electric PMC-630 E User Manual Download Page 49](http://html1.mh-extra.com/html/ceiec-electric/pmc-630-e/pmc-630-e_user-manual_2579014049.webp)
49
Ceiec Electric Technology
Register
Property
Description
Format
Unit
0200
RW
kWh Import
UINT32
kWh
0202
RW
kWh Export
UINT32
kWh
0204
RO
kWh Net
INT32
kWh
0206
RO
kWh Total
UINT32
kWh
0208
RW
kvarh Import
UINT32
kvarh
0210
RW
kvarh Export
UINT32
kvarh
0212
RO
kvarh Net
INT32
kvarh
0214
RO
kvarh Total
UINT32
kvarh
0216
RW
kVAh
UINT32
kVAh
Table 5-3 Energy Measurements
5.1.3 Pulse Counter
The Pulse Counter data returned is 1000 times the actual value. For example, if the register contains
a value of 1234567, the actual counter value is 1234.567.
Register
Property
Description
Format
0350
RW
Counter #1 (DI1)
UINT32
0352
RW
Counter #2 (DI2)
UINT32
0354
RW
Counter #3 (DI3)
UINT32
0356
RW
Counter #4 (DI4)
UINT32
0358
RW
Counter #5 (DI5)
UINT32
0360
RW
Counter #6 (DI6)
UINT32
Table 5-4 Pulse Counter
5.1.4 Harmonic Measurements
The Harmonics data (Individual Harmonics, THD, TOHD and TEHD) returned is 10000 times the actual
value. For example, if the register contains a value of 1031, the actual harmonic value is 0.1031 or
10.31%. The K Factor data is returned is 10 times the actual value.
Register
Property
Description
Format
Scale/Unit
0450
RO
dPFa
1
Float
0452
RO
dPFb
1
Float
0454
RO
dPFc
1
Float
0456
RO
dPF Total
1
Float
0458
RO
Ia K Factor
UINT16
×10
0459
RO
Ib K Factor
UINT16
×10
0460
RO
Ic K Factor
UINT16
×10
0461
RO
Va THD
UINT16
×10000
0462
RO
Vb THD
UINT16
×10000
0463
RO
Vc THD
UINT16
×10000
0464
RO
Ia THD
UINT16
×10000
0465
RO
Ib THD
UINT16
×10000
0466
RO
Ic THD
UINT16
×10000