18
Ceiec Electric Technology
2.5 Communications Wiring
2.5.1 RS485 Port
The PMC-630E provides one RS485 port and supports the Modbus RTU and EGATE (Ethernet Serial
Gateway) protocol. Up to 32 devices can be connected on a RS485 bus. The overall length of the
RS485 cable connecting all devices should not exceed 1200m.
If the master station does not have a RS485 communications port, a RS232/RS485 or USB/RS485
converter with optically isolated outputs and surge protection should be used.
The following figure illustrates the RS485 communications connections on the PMC-630E:
Figure 2-11 RS485 Communications Connections
2.5.2 Ethernet Port (10/100BaseT)
RJ45 Connector
Pin
Meaning
1
Transmit Data+
2
Transmit Data-
3
Receive Data+
4, 5, 7, 8
NC
6
Receive Data-
Table 2-1 RJ45 Connector Pin Description for 10/100BaseT Applications
2.6 Digital Input Wiring
The following figure illustrates the Digital Input connections on the PMC-630E:
Figure 2-12 DI Connections