RW
Nominal Frequency
(f
nominal
)
UINT16
0=50Hz*
1=60Hz
6006
RW
Port 1 Protocol
UINT16
0=Modbus*
1= EGATE
6007
RW
Port 1 Unit ID
UINT16
1 to 247
(Default = 100)
6008
RW
Port 1 Baud rate
UINT16
0=1200
1=2400
2=4800
3=9600*
4=19200
5=38400
6009
RW
Port 1 Configuration
UINT16
0=8N2
1=8O1
2=8E1*
3=8N1
4=8O2
5=8E2
6010
RW
IP Address
UINT32
E.g. if the IP Address is
“192.168.0.100”, write
“0xC0A80064” to this register
(Default=192.168.0.100)
6012
RW
Subnet Mask
UINT32
E.g. if the Subnet Mask is
“255.255.255.0”, write
“0xFFFFFF00” to this register
(Default=255.255.255.0)
6014
RW
Gateway Address
UINT32
E.g. if the Gateway Address is
“192.168.0.1”, write
“0XC0A80001” to this register
(Default=192.168.0.1)
6016
RW
Power Factor Convention
UINT16
0=IEC*
1=IEEE
2=-IEEE
6017
RW
kVA Calculation
UINT16
0=Vector*
1=Scalar
6018
RW
Demand Period
UINT16
1 to 60 (minutes)
(Default = 15)
6019
RW
Number of Sliding
Windows
UINT16
1* to 15
6020
RW
DI1 Function
UINT16
0=Digital Input*
1=Pulse Counter
6021
RW
DI2 Function
UINT16
6022
RW
DI3 Function
UINT16
6023
RW
DI4 Function
UINT16
6024
RW
DI5 Function
UINT16