![CE+T Power T2S-ETH User Manual Download Page 80](http://html1.mh-extra.com/html/ce-t-power/t2s-eth/t2s-eth_user-manual_2577175080.webp)
Index
Name
Description
Type
25L
bNoEPC
Flag (true or false) that indicates if module has an AC input (EPC) or not
U8
26
wPoutNominalW
Nominal output power (W)
U16
27
wPoutNominalVA
Nominal output power (VA)
U16
28
wVinNominalAC
Nominal AC input voltage (0.1V)
U16
29
wVinNominalDC
Nominal DC input voltage (0.1V)
U16
30
wVinNominalFreqAC
Nominal AC frequency (0.1Hz)
U16
Phase table (0x0640)
The following table described represents the information that can be retrieved regarding a particular phase. Maximum
amount of phase is set to 8. Each of them is identified by a label ranging from 1 to 8.
BASE ADDRESS
: 600(0x0640) + 27*(Phase label – 1).
Index
Name
Description
Type
0H
bRatioAvailableW
Ratio between output load and available power in watts (%)
U8
0L
bRatioAvailableVA
Ratio between output load and available power in VA (%)
U8
1H
bRatioInstalledW
Ratio between output load and installed power (Nb modules –
redundancy) in watts (%)
U8
1L
bRatioInstalledVA
Ratio between output load and installed power (Nb modules –
redundancy) in VA (%)
U8
2
wVout
Output voltage value (0.1V)
U16
3
wIout
Output current value (0.1A)
U16
4H
bNbOndCfg
Number of modules configured in the phase
U8
4L
bRedundancy
Amount of redundancy configured in the phase
U8
5
wACOutFreq
AC output frequency value (0.1Hz)
U16
6
lPinDC
DC input power value (W)
U32
8
lPinACW
AC input power value (W)
U32
10
lPinACVA
AC input power value (VA)
U32
12
lCurrentPowerInVA
Output power value (VA)
U32
14
lCurrentPowerInW
Output power value (W)
U32
16
lInstalledPowerInW
Installed power value (W)
U32
18
lInstalledPowerInVA
Installed power value (VA)
U32
20
lAvailablePowerInW
Available power value (W)
U32
22
lAvailablePowerInVA
Available power value (VA)
U32
24H
bNbInvSeen
Number of module seen by T2S ETH in that phase
U8
24L
bNbInvOK
Number of modules that are delivering output in the phase
U8
25H
bNbInvMO
Number of modules manually off in the phase
U8
25L
bNbInvKO
Number of modules that are not delivering output due to a failure in the
phase
U8
80
– Monitoring T2S - ETH User Manual – v1.4
Annex 3: Modbus
Summary of Contents for T2S-ETH
Page 64: ...64 Monitoring T2S ETH User Manual v1 4 SNMP...
Page 96: ......