Address
Description
Unit
Type
1016
Total available AC output apparent power
VA
S32
1030
Total AC input true power
W
S32
1032
Total AC input apparent power
VA
S32
1034
Total DC input true power
W
S32
1080
Worse AC output load status
U16
1081
Worse AC output hardware status (inverters)
U16
1082
Reserved
1083
Reserved
1084
Worse AC input source status
U16
1085
Worse AC input hardware status
U16
1086
Worse DC input source status
U16
1087
Worse DC input hardware status
U16
1088
Redundancy lost
U16
1089
On DC
U16
1090
Reserved
U16
1091
MBP engaged
U16
1096
Number of events (all alarms types)
U16
1097
Number of major alarms
U16
1098
Number of minor alarms
U16
Output phase 1
2050
Phase 1 true power
W
S32/float
2052
Phase 1 apparent power
VA
S32/float
2054
Phase 1 voltage
V/10
S32/float
2056
Phase 1 current
A/10
S32/float
2058
Phase 1 frequency
Hz/100
S32/float
2060
Reserved
2062
Phase 1 worse power factor
%
S32/float
2064
Phase 1 worse temperature
°C/10
S32/float
2066
Phase 1 load ratio (W)
%
S32/float
2068
Phase 1 load ratio (VA)
%
S32/float
2070
Phase 1 available true power
W
S32/float
2072
Phase 1 available apparent power
VA
S32/float
Output phase 2
2100
Phase 2 true power
W
S32/float
2102
Phase 2 apparent power
VA
S32/float