16. Annex 3: Modbus
16.1 Hardware Requirements
16.1.1 Cabling:
ModBus RTU is available on the on RJ45 connector located on the back plane of the rack containing the T2S ETH
controller. The pin out of this connector is the following:
Pin Number
Name
Description
1
CANH
CANH pin for Candis
2
CANL
CANL pin for Candis
3
GND_IAX
Digital Communication Ground
4
GND_IAX
Digital Communication Ground
5
12V_IAX
+12 V unregulated
6
COM_A
RS 485 A
7
GND_IAX
Digital Communication Ground
8
COM_B
RS 485 B
16.1.2 Baud rate, parity and mode
Only RTU mode is supported.
Item
Value
Default
Slave address
From 1 to 247
1
Baud Rate
9600, 19200, 38400 or 115200
19200
Parity
Even, odd, none
Even
Stop bits
One, two
One
Mode
RTU
-
Electrical interface
RS485
-