DIGIWAY Plus is equipped with an innovative software which fits the internal parameters
DIGIWAY Plus is equipped with an innovative software which fits the internal parameters
to the door characteristics. The calibration sets the door travel limits and launches a
to the door characteristics. The calibration sets the door travel limits and launches a
special 5 cycle-routine for the automatic detection of the door characteristics.
special 5 cycle-routine for the automatic detection of the door characteristics.
For the calibration follow the next steps:
For the calibration follow the next steps:
Set the EXTERNAL SWITCH in posi-
tion ‘0’ ‘0’ = DOOR FREE
(*)
1
1
Action
Action
Display
Display
Select Door Calibration from the Main
Manu and press OK
2
2
CLOSE THE DOOR COMPLETELY
and press
OK
OPEN THE DOOR COMPLETELY
and
press OK
(*)
4
4
Select Autocalibration from the Door
Calibration Menu and press OK
5
5
6
6
Door Calibration
Door Limits
Close Door
Then Press OK
Open Door
Then Press OK
Thank You
Door Calibration
Autocalibration
Autocalibration
Wizard
Door Calibration
Select Door Limits from the submenu
of Door Calibration and press OK
3
3
Door Calibration
Door Limits
Set Door Limits
Wizard
STEP III: DOOR CALIBRATION [SINGLE LEAF]
(*) If this set is not followed, the software will give a warning.
NOTE: Before proceeding with the calibration check the connection of the battery red/
black cable to the main board and disconnect temporarily any lock if connected, Make
sure any door latch is retracted to allow clear operation of the door movement.
ATTENTION: Any change carried out requires a complete cycle (open, pause,
ATTENTION: Any change carried out requires a complete cycle (open, pause,
close) or a system reset to be implemented.
close) or a system reset to be implemented.
Proceed with
Autocalibration?