80
REVO C
3PH from 1100A to 2100A
User’s manual
15.2 Current Limit tuning procedure
• Give the power supply and set the current limit to zero:
- In analog mode, set the analog input 2 to zero
- In digital mode, set the parameter=0
• Start the thyristor unit.
• Set the primary input or the setpoint value at 100%
• Increase the current limit
- In analog mode increase the value of the analog input
- In digital mode increase the parameter until to reach the desired value of rms current.
• Stop the thyristor unit.
The Current Limit Procedure is done.
Use the configurator software to set the desired current limit value.
Summary of Contents for REVO C 3PH 1100A