50
REVO C
3PH from 1100A to 2100A
User’s manual
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Retransmit
Choose which parameter is retransmitted by the
analog output
12
68
Read
Write
Option
Description
Value
Set Point
Set point
15
Volts Out
RMS voltage output
10
Power
Average output power
12
Current
RMS current output
11
None
Do not retransmit value
0
DEFAULT:
Power
12
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Rtx Scale
Set the value of retransmitted
parameter to be represented by
the full scale of the analog output.
See the table below
0
0 to 9999
124
Read
Write
Retransmit
Recommended
Retransmission
Scaling
Resulting Signal
(4 to 20 mADC)
Resulting Signal
(0 to 20 mADC)
Resulting Signal
(0 to 10 VDC)
Max Value
Set Point
100
4mADC = 0%
20mADC = 100%
0mADC = 0%
20mADC = 100%
0VDC = 0%
10VDC = 100%
100.0
V Output
xV
where
x
is the
Nominal Line
Voltage
4mADC = 0V
20mADC = xV
0mADC = 0V
20mADC = xV
0VDC = 0V
10VDC = xV
999.9
I Output
xA
where
x
is
the Nominal Line
Current
4mADC = 0A
20mADC = xA
0mADC = 0A
20mADC = xA
0VDC = 0A
10VDC = xA
999.9
Power
100
4mADC = 0%
20mADC = 100%
0mADC = 0%
20mADC = 100%
0VDC = 0%
10VDC = 100%
100