REVO C
3PH from 1100A to 2100A
User’s manual
89
Internal Fuse
The thyristor unit have internal fuse extrarapid at low I
2
T for the thyristor protection of against the short-circuits.
The Fuses must have I
2
T 20% less than thyristor’s I
2
T. The warranty of thyristor is null if no proper fuses are used.
Remove cover, remove screws and fuses.
TORQUE for M12 fuse screws min: 32 Nm to Max: 52 Nm
600V
Thyristor
Size
Fuse CODE
200 kA
RMS
Symmetrical A.I.C.
Qty for
each
Phase
Total
Current
(A
RMS
)
Power
Loss (W)
FUSE I
2
T value
Suggested A2s
(at 660V)*
Vac
1100A
FU800SIBSQB3690700V
800
118
480.000
690
2
1400A
FU1250SIBSQB3690700V
1250
147
1.750.000
690
2
1600A
FU1400SIBSQB3690700V
1400
161
2.200.000
690
2
1800A
FU1400SIBSQB3690700V
1400
161
2.200.000
690
2
2100A
FU1600SIBSQB3 600V
1600
190
3.700.000
600
2
*I
2
T are multiplied for K value in function of Vac at 500V K is equal to 0,7
(ex:480.000 X 0,7 = 336.000). At 660 Vac K is equal to 1.
690V
Thyristor
Size
Fuse CODE
200 kA
RMS
Symmetrical A.I.C.
Qty for
each
Phase
Total
Current
(A
RMS
)
Power
Loss (W)
FUSE I
2
T value
Suggested A2s
(at 1000V)*
Vac
1100A
FU1000SIBSQB31000V
1000
150
1.900.000
1000
2
1400A
FU1250SIBSQB3900V
1250
198
3.300.000
900
2
1600A
FU1400SIBSQB3900V
1250
210
3.900.000
900
2
1800A
FU1400SIBSQB3900V
1400
210
3.900.000
900
2
2100A
FU1400SIBSQB3900V
1400
210
3.900.000
900
2
*I
2
T are multiplied for K value in function of Vac at 700V K is equal to 0,73
(ex: 1.900.000 X 0,73= 1.387.000). At 1000 Vac K is equal to 1.
24
Summary of Contents for REVO C 3PH 1100A
Page 2: ......