8.
CHECKS TO MAKE BEFORE POWER IS CONNECTED TO THE UNIT
1.
Setting and checks before the power is turned ON
1)
Set the door opening direction by the selector (L: Left Hand, R: Right Hand)
provided on the microcomputer control box CS005
(PAGE 7)
DO NOT CHANGE SWITCH WHILE POWER IS ON TO AVOID CONTROLLER
DAMAGE
Turn power OFF, wait 5 sec to drain power. Change setting and reconnect
power.
2)
Make sure ‘HOLD OPEN’ adjustment pot is set to the desired position.
3)
Manually check smooth running of the door by pushing it between the open
and closed positions.
5) Check whether all wires are fully connected to the proper positions. Check the
activation wires are connected properly into the transformer input plugs.
4)
Check that there is no looseness or other problems with the rest of the
componentry regarding screws and wires.
5)
Move door to the centre of the opening – ready to connect the power.
2.
Initial movement at power ON
1)
When power is turned ON, the red LED display shows door opening and
closing times.
2)
The door moves according to dip switch 6
3)
During the initial movement –
When activation devices are off
- The door when fully open, starts closing after the pre-set hold open period.
- When closed, the microcomputer memorises the distance the door has
traveled to the closed position.
- The slow close distance is then automatically set by the microcomputer.
4)
Pushing the test button TB allows opening and closing automatically of the
door.
5)
Set the HOLD TIMER (SEC), CLOSING SPEED (MM/SEC) and SECOND
DISTANCE (%).
NOTE:
If for any reason the distance the door is required to travel has changed, then the
controller setting will need to be relearnt. Turn OFF the power and turn ON again after
5 seconds. The door will start the initial learning movement and then follow the normal
operation procedure.