DIP SWITCH 8: LOCK LK001 or LK002
Selected by the lock LK001 type, or Hypoid lock (LK002) which is connected to the 4pin
male connector plug on the microcontroller.
State
Setting
ON (UP)
DL TYPE: The lock DL type (or PL type) is connected.
OFF (DOWN)
KL TYPE: The Hypoid lock type is connected.
NOTE:
The DIP switches are pre-set when delivered. Take a photo of your setting before
attempting to reset the cycle count. Remember to remove the power from the
controller when adjusting dip switch settings.
HOW TO RESET THE CYCLE COUNT
- Turn DIP SWITCH
⑥
ON/UP if the digital counter is to be reset.
- Hold Test Button for 3 seconds
- Cycle count will reset
- Door will start a new learning sequence to find open and closed positions.
If dip switch 6 is OFF/Down when the test button is pressed the door will only start a
new learning sequence for open and closed positions. The cycle count will NOT be
reset.