Operating Range is Short
If all PSDs have the same issue, see the
Error! Reference source not found
section above. If only one PSD
has the problem, the PSD is faulty. Return to Cattron or an authorized service facility.
MSD
Error Light is Flashing
If switching the MSD off and back on does not resolve the problem, return to Cattron or an authorized service
facility.
No Power
If all lights are off, request the services of an authorized and trained service agent to conduct the following
analysis and repair:
Verify that the 24Vdc input supply is available and, if necessary, check and replace the fuse to the left of the
supply terminal.
If the fuse blows again, disconnect all input and output terminals and replace the fuse again. If the problem
persists, the MSD is faulty. Return to Cattron or an authorized service facility. If the fuse no longer blows, check
all external wiring for an intermittent short circuit on the 24V line and correct.
Operating Range is Short
If all PSDs have the same issue see
Error! Reference source not found
section above.
Cannot Reset Unit after a PSD Communication Loss
Check the wiring and voltages between the reset input, the external reset button, and the 24V supply to the reset
button. If this supply is not common to the MSD supply, ensure the 0v line of the external supply is connected to
the 0V line of the MSD supply.
Battery Charger
Chargers don’t generally require maintenance, but in the event of damage to the unit, the external power supply,
or the cable, contact Cattron customer service for a replacement.
Make sure contacts in charging pod and on the PSD are clean. If contacts require cleaning, disconnect charger
from power supply and wipe with a dry, lint free cloth.
Do not charge PSD batteries at temperatures below 0° Celsius or above 40° Celsius.