ECONOMIZER MODULE WIRING DETAILS
Use Fig. 71 and Tables 22 and 23 to locate the wiring terminals
for the Economizer module.
NOTE: The four terminal blocks are removable. Slide out each
terminal block, wire it, and then slide it back into place.
Fig. 71 — W7220 Wiring Terminals
*Sylk is a trademark of Honeywell International Inc.
S-Bus Sensor Wiring
The labels on the sensors and controller are color coded for
ease of installation. Orange labeled sensors can only be wired
to orange terminals on the controller. Brown labeled sensors
can only be wired to S-bus (brown) terminals. Use Fig. 72 and
Table 24 to locate the wiring terminals for each S-Bus and en-
thalpy control sensor.
Fig. 72 — S-Bus Sensor DIP Switches
Table 22 — Economizer Module
(Left Hand Terminal Blocks)
LABEL
TYPE
DESCRIPTION
Top Left Terminal Block
MAT
MAT
20k NTC
and COM
Mixed Air Temperature Sensor (Polarity
Insensitive Connection)
OAT
OAT
20k NTC
and COM
Outdoor Air Temperature Sensor (Polarity
Insensitive Connection)
S-BUS
S-BUS
S-BUS
(Sylk* Bus)
Enthalpy Control Sensor
(Polarity Insensitive Connection)
Bottom Left Terminal Block
IAQ 2-10
2-10 vdc
Air Quality Sensor Input (e.g. CO
2
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 vac
Air Quality Sensor 24 vac Source
ACT 2-10
2-10 vdc
Damper Actuator Output (2-10 vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24v
24 vac
Damper Actuator 24 vac Source
NA
AUX2-
OCC
E-GND
EXH1
AUX1-O
Y2-
Y1-
Y2-O
Y1-O
C
R
5004
88
4
8
-002
Rev. A
NA
A2
OCC
EX
A1
Y2I
Y2O
Y1I
Y1O
C
R
MAT
MAT
OAT
OAT
S
-BU
S
S
-BU
S
IAQ 2-10
IAQCOM
IAQ 24V
ACT 2-10
ACT COM
ACT 24V
MA
MA
OA
OA
S
B
S
B
S
B
S
B
S
B
S
B
V
C
R
V
C
R
NA
50040
83
9-001
Rev. G
HJW10
www.energy.c
a
.gov
Certified FDD Prod
u
ct
C
a
liforni
a
Title 24, P
a
rt 6
Table 23 — Economizer Module
(Right Hand Terminal Blocks)
LABEL
TYPE
DESCRIPTION
Top Right Terminal Blocks
AUX2 I
24 vac IN
The first terminal is not used.
OCC
24 vac IN
Shut Down (SD) or HEAT (W)
Conventional only
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
E-GND
E-GND
Occupied/Unoccupied Input
EXH1
24 vac OUT
Exhaust Fan 1 Output
AUX1 O
24 vac OUT
Programmable:
Exhaust fan 2 output
or
ERV
or
System alarm output
Bottom Right Terminal Blocks
Y2-I
24 vac IN
Y2 in - Cooling Stage 2 Input from space
thermostat
Y2-O
24 vac OUT
Y2 out - Cooling Stage 2 Output to stage
2 mechanical cooling
Y1-I
24 vac IN
Y1 in - Cooling Stage 2 Input from space
thermostat
Y1-O
24 vac OUT
Y1 out - Cooling Stage 2 Output to stage
2 mechanical cooling
C
COM
24 vac Common
R
24 vac
24 vac Power (hot)
DIP
SWITCH
LABEL
DIP
SWITCHES
(3)
S-BUS
2 PIN SIDE
CONNECTOR
S-BUS
TERMINALS
(1 AND 2)
Summary of Contents for WeatherMaster Puron 48HC D17
Page 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Page 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Page 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Page 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Page 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Page 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Page 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Page 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Page 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Page 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Page 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Page 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Page 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Page 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Page 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Page 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Page 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Page 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Page 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Page 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Page 97: ......