
51
Fig. 66 — Return-Air Temperature or Enthalpy
Sensor Mounting Location
OUTDOOR ENTHALPY CHANGEOVER
For enthalpy control, accessory enthalpy sensor (part number
HH57AC078) is required. Replace the standard outdoor dry
bulb temperature sensor with the accessory enthalpy sensor in
the same mounting location. (See Fig. 67.) When the outdoor
air enthalpy rises above the outdoor enthalpy changeover set-
point, the outdoor-air damper moves to its minimum position.
The outdoor enthalpy changeover setpoint is set with the out-
door enthalpy setpoint potentiometer on the EconoMi$er IV
controller. The setpoints are A, B, C, and D. (See Fig. 68.) The
factory-installed 620-ohm jumper must be in place across ter-
minals SR and SR+ on the EconoMi$er IV controller.
Fig. 67 — Enthalpy Changeover Setpoints
Fig. 68 — EconoMi$er IV Control
DIFFERENTIAL ENTHALPY CONTROL
For differential enthalpy control, the EconoMi$er IV controller
uses two enthalpy sensors (HH57AC078 and CRENT-
DIF004A00), one in the outside-air duct and one in the return-
air duct. The EconoMi$er IV controller compares the outdoor
air enthalpy to the return air enthalpy to determine EconoMi$er
IV use. The controller selects the lower enthalpy air (return or
outdoor) for cooling. For example, when the outdoor air has a
lower enthalpy than the return air, the EconoMi$er IV opens to
bring in outdoor air for free cooling.
Replace the standard outside air dry bulb temperature sensor
with the accessory enthalpy sensor in the same mounting loca-
tion. See Fig. 56. Mount the return air enthalpy sensor in the
return air duct. See Fig. 66. Wiring is provided in the
EconoMi$er IV wiring harness. See Fig. 59. The outdoor en-
thalpy changeover setpoint is set with the outdoor enthalpy set-
point potentiometer on the EconoMi$er IV controller. When
using this mode of changeover control, turn the enthalpy set-
point potentiometer fully clockwise to the D setting.
INDOOR AIR QUALITY (IAQ) SENSOR INPUT
The IAQ input can be used for demand controlled ventilation
control based on the level of CO
2
measured in the space or re-
turn air duct.
Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
AQ1 terminals of the controller. Adjust the DCV potentiome-
ters to correspond to the DCV voltage output of the indoor air
quality sensor at the user-determined setpoint. See Fig. 69.
If a separate field-supplied transformer is used to power the
IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
When using demand ventilation, the minimum damper position
represents the minimum ventilation position for VOC (volatile or-
ganic compounds) ventilation requirements. The maximum de-
mand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the mini-
mum position potentiometer should be used to set the occupied
ventilation position. The maximum demand ventilation posi-
tion should be turned fully clockwise.
ECONOMI$ER IV
ECONOMI$ER IV
CONTROLLER
GROMMET
RETURN AIR
S
EN
S
OR
RETURN DUCT
CONTROL
CURVE
A
B
C
D
CONTROL POINT
APPROX.
deg. F (deg. C)
AT 50
%
RH
73 (23)
70 (21)
67 (19)
63 (17)
12
14
16
1
8
20
2
2
2
4
2
6
28
30
32
3
4
3
6
38
40
4
2
4
4
46
9
0
1
0
0
80
7
0
60
50
40
30
20
10
E
NTHALPY
BTU PER
POUN
D DRY
AI
R
85
(29)
90
(32)
95
(35)
100
(38)
105
(41)
110
(43)
3
5
(2)
35
(2)
40
(4)
40
(4)
105
(41)
110
(43)
45
(7)
45
(7)
50
(10)
50
(10)
55
(13)
55
(13)
60
(16)
60
(16)
65
(18)
65
(18)
70
(21)
70
(21)
75
(24)
75
(24)
80
(27)
80
(27)
85
(29)
90
(32)
95
(35)
100
(38)
A
A
B
B
C
C
D
D
RELA
TI
VE HUMI
DI
TY (
%
)
HIGH LIMIT
CURVE
TR1
24 V
a
c
COM
TR
24
V
a
c
HOT
1
2
3
4
5
EF
EF1
+
_
P1
T1
P
T
N
EXH
2V
10V
EXH
S
et
S
et
2V
10V
2V
10V
DCV
DCV
Free
Cool
B
C
A
D
S
O+
S
R+
S
R
S
O
AQ1
AQ
DCV
Min
Po
s
Open
M
a
x
N1
Summary of Contents for WeatherMaster Puron 48HC D17
Page 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Page 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Page 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Page 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Page 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Page 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Page 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Page 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Page 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Page 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Page 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Page 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Page 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Page 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Page 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Page 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Page 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Page 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Page 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Page 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Page 97: ......