60
SETPOINTS
(cont)
VENTMIN 2.25
V
2 to 10 vdc or 100
to 9990 cfm
increment by 10
DCV MINIMUM DAMPER POSITION
Displays only if a CO
2
sensor is connected. Used for Va
(ventilation min cfm) set point. This is the ventilation for less than
maximum occupancy of the space.
100 to 9990 cfm;
increment by 10
If OA, MA, RA, and CO
2
sensors are connected and DCV CAL
ENABLE is set to AUTO mode, the OA dampers are controlled
by CFM and displays from 100 to 9990 CFM.
2 to 10 vdc
With 2-speed fan units VENTMIN L (low speed fan) and
VENTMIN H (high speed fan) settings are required. Default for
VENTMIN L is 2.5V and VENTMIN H is 2.25V
ERV OAT SP
††
32°F (0°C)
0°F to 50°F
(–18°C to 10°C);
increment by
1 degree
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR
TEMPERATURE SETPOINT
Only when AUX1 O = ERV
EXH1 SET
50%
0 to 100%;
increment by 1
EXHAUST FAN STAGE 1 SETPOINT
Set point for OA damper position when exhaust fan 1 is powered
by the economizer.
With 2-speed fan units, Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1 L is 65% and
Exh1 H is 50%
EXH2 SET
75%
0 to 100%;
increment by 1
EXHAUST FAN STAGE 2 SETPOINT
Set point for OA damper position when exhaust fan 2 is powered
by the economizer. Only used when AUX1 O is set to EHX2.
With 2-speed fan units, Exh2 L (low speed fan) and Exh2 H (high
speed fan) settings are required. Default for Exh2 L is 80% and
Exh2 H is 75%
SYSTEM
SETUP
INSTALL
01/01/10
N/A
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG
°F
°F or °C
Sets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENT
CONV
CONV
or
HP
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller.
AUX2 IN
W
Shutdown (SD)
Heat (W1)
HP(O)
HP(B)
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV
mode for W. Shutdown is not available in 2-speed fan mode.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
FAN SPEED
2 speed
1 speed/2 speed
Sets the economizer controller for operation of 1 speed or 2
speed supply fan. The controller does not control the fan, but
positions the OA and RA dampers to heating or cooling mode.
NOTE: 2-speed fan option also needs Heat (W1) programmed in
AUX 2 In.
FAN CFM
5000 cfm
100 to 15000 cfm;
increment by 100
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVCAL ENA = AUTO
This is the capacity of the RTU. The value is found on the
nameplate label for the specific unit.
AUX1 OUT
NONE
NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
††
• EXH2 = second damper position 24 vac out for second exhaust
fan
• SYS = use output as an alarm signal
OCC
INPUT
INPUT or ALWAYS
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac),
the 24 vac is input “INPUT” to the OCC terminal. If no occupancy
output from the thermostat, then change program to “ALWAYS”
OR add a jumper from terminal R to OCC terminal.
FACTORY DEFAULT
NO
NO or YES
Resets all set points to factory defaults when set to YES. LCD
will briefly flash YES and change to NO but all parameters will
change to the factory default values.
ADVANCED
SETUP
MA LO SET
45°F (7°C)
35°F to 65°F
(2°C to 18°C);
Increment by
1 degree
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to activate Freeze Protection (close damper or
modulate to MIN POS if temp falls below set value).
FREEZE POS
CLO
CLO or MIN
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN
POS).
CO2 ZERO
0ppm
0 to 500 ppm;
Increment by 10
CO
2
ppm level to match CO
2
sensor start level.
CO2 SPAN
2000ppm
1000 to 3000 ppm;
Increment by 50
CO
2
ppm span to match CO
2
sensor; e.g.: 500-1500 sensor
output would be 500 CO
2
zero and 1000 CO
2
span.
Table 26 — W7220 Menu Structure* (cont)
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
EXPANDED PARAMETER NAME
Notes
Summary of Contents for WeatherMaster Puron 48HC D17
Page 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Page 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Page 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Page 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Page 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Page 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Page 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Page 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Page 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Page 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Page 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Page 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Page 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Page 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Page 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Page 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Page 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Page 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Page 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Page 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Page 97: ......