70
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temperature
lever above room temperature.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then there is
a 22 second delay before another 5 second try. If the
burner still does not light, the time delay is repeated. If the
burner does not light within 15 minutes, there is a lockout.
To reset the control, break the 24 v power to W1.
6. The evaporator-fan motor will turn on 45 seconds after
burner ignition.
7. The evaporator-fan motor will turn off in 45 seconds after
the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the
range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor on/off de-
lay is 45 seconds. The Integrated Gas Unit Controller (IGC) modi-
fies this value when abnormal limit switch cycles occur. Based
upon unit operating conditions, the on delay can be reduced to
0 seconds and the off delay can be extended to 180 seconds. When
one flash of the LED is observed, the evaporator-fan on/off delay
has been modified.
If the limit switch trips at the start of the heating cycle during
the evaporator on delay, the time period of the on delay for the
next cycle will be 5 seconds less than the time at which the
switch tripped. (Example: If the limit switch trips at
30 seconds, the evaporator-fan on delay for the next cycle will
occur at 25 seconds.) To prevent short-cycling, a 5 second re-
duction will only occur if a minimum of 10 minutes has
elapsed since the last call for heating.
The evaporator-fan off delay can also be modified. Once the
call for heating has ended, there is a 10 minute period during
which the modification can occur. If the limit switch trips
during this period, the evaporator-fan off delay will increase by
15 seconds. A maximum of 9 trips can occur, extending the
evaporator-fan off delay to 180 seconds.
To restore the original default value, reset the power to the unit.
To shut off unit, set system selector switch at OFF position.
Resetting heating selector lever below room temperature will
temporarily shut unit off until space temperature falls below
thermostat setting.
VENTILATION (CONTINUOUS FAN)
Set fan and system selector switches at ON and OFF positions,
respectively. Evaporator fan operates continuously to provide
constant air circulation. When the evaporator-fan selector
switch is turned to the OFF position, there is a 30 second delay
before the fan turns off.
FASTENER TORQUE VALUES
Table 38 — Torque Values
FASTENER LOCATIONS
TORQUE VALUES
Supply fan motor mounting
120 in.-lbs (13.6 Nm) ± 12 in.-lb
(1.4Nm)
Supply fan motor adjustment
plate
120 in.-lbs (13.6 Nm) ± 12 in.-lb
(1.4Nm)
Motor pulley setscrew
72 in.-lbs (8.1 Nm) ± 5 in.-lb
(0.6 Nm)
Fan pulley setscrew
72 in.-lbs (8.1 Nm) ± 5 in.-lb
(0.6 Nm)
Blower wheel hub setscrew
72 in.-lbs (8.1 Nm) ± 5 in.-lb
(0.6 Nm)
Bearing locking collar setscrew
50 in.-lbs (6.2 Nm) – 60 in.-lb
(6.8 Nm)
Compressor mounting bolts
65 in.-lbs (7.3 Nm) – 75 in.-lb
(8.5Nm)
Condenser fan motor mounting
bolts
20 in.-lbs (2.3 Nm) ± 2 in.-lb
(0.2 Nm)
Condenser fan hub setscrew
84 in.-lbs (9.5 Nm) ± 12 in.-lb
(1.4 Nm)
Summary of Contents for WeatherMaster Puron 48HC D17
Page 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Page 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Page 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Page 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Page 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Page 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Page 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Page 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Page 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Page 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Page 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Page 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Page 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Page 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Page 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Page 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Page 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Page 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Page 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Page 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Page 97: ......