79
Boldface
indicates an alternated standard static drive package is
re
q
uired.
Italics
indicate a high static drive package with different motor pulley is
re
q
uired.
Table H — 48HCF*24 Vertical Supply (20 Tons)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6000
615
1.25
690
1.56
757
1.89
819
2.22
875
2.57
6500
653
1.52
725
1.87
789
2.21
848
2.57
903
2.94
7000
692
1.85
760
2.21
822
2.58
879
2.96
932
3.35
7500
731
2.21
796
2.60
856
3.00
911
3.40
963
3.81
8000
771
2.63
833
3.04
890
3.47
944
3.89
994
4.33
8500
812
3.10
871
3.54
926
3.98
977
4.43
1026
4.89
9000
852
3.62
909
4.09
961
4.55
1011
5.03
1059
5.51
9500
893
4.20
947
4.69
998
5.19
1046
5.69
1092
6.19
10000
934
4.85
986
5.36
1035
5.88
1082
6.40
1126
6.93
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6000
928
2.92
978
3.28
1025
3.65
1071
4.03
1114
4.42
6500
955
3.31
1003
3.69
1050
4.09
1094
4.49
1137
4.89
7000
983
3.75
1030
4.15
1075
4.56
1119
4.98
1161
5.41
7500
1011
4.23
1058
4.66
1102
5.09
1145
5.53
1186
5.98
8000
1041
4.77
1087
5.21
1130
5.67
1171
6.13
—
—
8500
1072
5.35
1116
5.82
1158
6.30
—
—
—
—
9000
1104
6.00
1147
6.49
1188
6.99
—
—
—
—
9500
1136
6.70
1178
7.22
—
—
—
—
—
—
10000
1169
7.47
—
—
—
—
—
—
—
—
Standard static 690-863 RPM
Voltage 208v / 230v / 460v / 575v
Max BHP 6.5 / 6.9 / 7.0 / 8.3
Medium static 835-1021 RPM
Voltage 208v / 230v / 460v / 575v
Max BHP 6.5 / 6.9 / 7.0 / 8.3
High static 941-1176 RPM
Voltage 208v / 230v / 460v / 575v
Max BHP 10.5 / 11.9 / 11.9 / 11.0
Summary of Contents for WeatherMaster Puron 48HC D17
Page 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Page 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Page 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Page 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Page 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Page 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Page 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Page 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Page 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Page 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Page 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Page 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Page 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Page 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Page 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Page 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Page 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Page 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Page 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Page 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Page 97: ......