CL-5
ITEM
EXPANSION
RANGE
DEFAULT
ENTRY
SW.LG
SWITCH LOGIC: NO / NC
FTS.L
Filter Status Inpt-Clean
Open/Close
Open
IGC.L
IGC Feedback - Off
Open/Close
Open
RMI.L
RemSw Off-Unoc-Strt-NoOv
Open/Close
Open
ECS.L
Economizer Switch - No
Open/Close
Open
SFS.L
Fan Status Sw. - Off
Open/Close
Open
DL1.L
Dmd.Lmt.Sw.1 - Off
Open/Close
Open
DL2.L
Dmd.Lmt.-Dehumid - Off
Open/Close
Open
IAQ.L
IAQ Disc.Input - Low
Open/Close
Open
FSD.L
Fire Shutdown - Off
Open/Close
Open
PRS.L
Pressurization Sw. - Off
Open/Close
Open
EVC.L
Evacuation Sw. - Off
Open/Close
Open
PRG.L
Smoke Purge Sw. - Off
Open/Close
Open
DISP
DISPLAY CONFIGURATION
TEST
Test Display LEDs
ON/OFF
Off
METR
Metric Display
ON/OFF
Off
LANG
Language Selection
0-1(multi-text strings)
0
PAS.E
Password Enable
ENABLE/DISABLE
Enable
PASS
Service Password
0000-9999
1111
Summary of Contents for WEATHERMAKER 48/50AJ
Page 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Page 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Page 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Page 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Page 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Page 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Page 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Page 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Page 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Page 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...