150
APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
TEMPS
Air Temp Lvg Supply Fan
dF
SAT
Return Air Temperature
dF
RAT
forcible
Outside Air Temperature
dF
OAT
forcible
Space Temperature
dF
SPT
forcible
Space Temperature Offset
^F
SPTO
forcible
Staged Gas LAT Sum
dF
LAT_SGAS
Staged Gas LAT 1
dF
LAT1SGAS
Staged Gas LAT 2
dF
LAT2SGAS
Staged Gas LAT 3
dF
LAT23SGAS
Staged Gas Limit Sw.Temp
dF
LIMSWTMP
Cir A Sat.Condensing Tmp
dF
SCTA
Cir B Sat.Condensing Tmp
dF
SCTB
Cir A Sat.Suction Temp.
dF
SSTA
Cir B Sat.Suction Temp.
dF
SSTB
TSTAT
Control Mode………..:
ascii text strings
Thermostat Y1 Input
On/Off
Y1
forcible
Thermostat Y2 Input
On/Off
Y2
forcible
Thermostat W1 Input
On/Off
W1
forcible
Thermostat W2 Input
On/Off
W2
forcible
Thermostat G Input
On/Off
G
forcible
UINPUTS
Filter Status Input
Dirty/Clean
FLTS
forcible
Fan request from IGC
On/Off
IGCFAN
Fire Shutdown Switch
Alarm/Normal
FSD
forcible
Thermostat G Input
On/Off
G
forcible
Thermostat W2 Input
On/Off
W2
forcible
Thermostat W1 Input
On/Off
W1
forcible
Thermostat Y2 Input
On/Off
Y2
forcible
Thermostat Y1 Input
On/Off
Y1
forcible
Economizer Control Input
On/Off
ECOSW
forcible
Remote Economizer Enable
Yes/No
ECONENBL
forcible
Econo Position Override
Yes/No
ECOORIDE
forcible
Remote Input State
On/Off
RMTIN
forcible
Supply Fan Status Switch
On/Off
SFS
forcible
Demand Limit Switch 1
On/Off
DMD_SW1
forcible
Demand Limit Switch 2
On/Off
DMD_SW2
forcible
Pressurization Input
Alarm/Normal
PRES
forcible
Evacuation Input
Alarm/Normal
EVAC
forcible
Smoke Purge Input
Alarm/Normal
PURG
forcible
IAQ - Discrete Input
High/Low
IAQIN
forcible
Dehumidify Switch Input
On/Off
DHDISCIN
forcible
UOUTPUTS
FANS
Supply Fan Relay
On/Off
SFAN_RLY
Supply Fan VFD Speed
0-100
%
SFAN_VFD
Supply Fan Request
Yes/No
SFANFORC
forcible
Power Exhaust Relay A
On/Off
PE_A
Power Exhaust Relay B
On/Off
PE_B
Power Exhaust Relay C
On/Off
PE_C
Condenser Fan A
On/Off
CONDFANA
Condenser Fan B
On/Off
CONDFANB
COOLING
Compressor A1 Relay
On/Off
CMPA1
Compressor A2 Relay
On/Off
CMPA2
Minimum Load Valve
On/Off
MLV
Compressor B1 Relay
On/Off
CMPB1
Compressor B2 Relay
On/Off
CMPB2
HEATING
Heat Relay 1
On/Off
HS1
Heat Relay 2
On/Off
HS2
Relay 3 W1 Gas Valve 2
On/Off
HS3
Relay 4 W2 Gas Valve 2
On/Off
HS4
Relay 5 W1 Gas Valve 3
On/Off
HS5
Relay 6 W2 Gas Valve 3
On/Off
HS6
Heat Interlock Relay
On/Off
HIR
forcible
ECONOMIZER
Economizer Act.Curr.Pos.
0-100
%
ECONOPOS
Economizer Act.Cmd.Pos.
0-100
%
ECONOCMD
forcible
Economizer Power Relay
On/Off
ECON_PWR
forcible
GENERAL OUTPUTS
Remote Alarm/Aux Relay
On/Off
ALRM
forcible
Summary of Contents for WEATHERMAKER 48/50AJ
Page 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Page 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Page 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Page 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Page 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Page 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Page 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Page 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Page 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Page 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...