APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE
NAME
RANGE
UNITS
POINT NAME
DEFAULT
COOL
Capacity Threshold Adjust
–10 -> 10
Z_GAIN
1
Compressor Lockout Temp
–20 -> 55
dF
OATLCOMP
40
Fan-off Delay, Mech Cool
0-600
sec
COOL_FOD
60
Minimum Load Valve?
Yes/No
MLV_SEL
No
Motor Master Control ?
Yes/No
MOTRMAST
No
Head Pressure Setpoint
80-150
dF
HPSP
110
Enable Compressor A1
Enable/Disable
CMPA1ENA
Enable
Enable Compressor A2
Enable/Disable
CMPA2ENA
Enable
Enable Compressor B1
Enable/Disable
CMPB1ENA
Enable
Enable Compressor B2
Enable/Disable
CMPB2ENA
Enable
CSB A1 Feedback Alarm
Enable/Disable
CSB_A1EN
Enable
CSB A2 Feedback Alarm
Enable/Disable
CSB_A2EN
Enable
CSB B1 Feedback Alarm
Enable/Disable
CSB_B1EN
Enable
CSB B2 Feedback Alarm
Enable/Disable
CSB_B2EN
Enable
Rev. Rotation Verified ?
Yes/No
REVR_VER
No
Hi SST Alert Delay Time
5-30
min
HSSTTIME
10
DEHU
Dehumidification
Config
0-2
DHSELECT
0
Dehumidification
Sensor
1-2
DHSENSOR
1
Econ disable in DH mode?
Yes/No
DHECONEN
No
Vent Reheat Setpt Select
0-1
DHVHTCFG
0
Vent Reheat RAT offset
0-8
^F
DHVRAOFF
0
Vent
Reheat
Setpoint
55-95
dF
DHVHT_SP
70
Dehumidify
Cool
Setpoint
40-55
dF
DHCOOLSP
45
Dehumidify
RH
Setpoint
10-90
%
DHRELHSP
55
DISP
Metric Display
Off/On
DISPUNIT
Off
Language Selection
0-1
LANGUAGE
0
Password Enable
Enable/Disable
PASS_EBL
Enable
Service Password
0000-9999
PASSWORD
1111
Contrast Adjustment
–255 - 255
CNTR_ADJ
0
Brightness Adjustment
–255 - 255
BRTS_ADJ
0
DLVT
Dmd Level Lo Heat On
–1 - 2
^F
DMDLHON
1.5
Dmd Level(+) Hi Heat On
0.5 - 20.0
^F
DMDHHON
0.5
Dmd Level(-) Lo Heat Off
0.5 - 2
^F
DMDLHOFF
1
Dmd Level Lo Cool On
–1 - 2
^F
DMDLCON
1.5
Dmd Level(+) Hi Cool On
0.5 - 20.0
^F
DMDHCON
0.5
Dmd Level(-) Lo Cool Off
0.5 - 2
^F
DMDLCOFF
1
Cool Trend Demand Level
0.1 - 5
^F
CTRENDLV
0.1
Heat Trend Demand Level
0.1 - 5
^F
HTRENDLV
0.1
Cool Trend Time
30 - 600
sec
CTRENDTM
120
Heat Trend Time
30 - 600
sec
HTRENDTM
120
DMDL
Demand Limit Select
0 - 3
DMD_CTRL
0
Demand Limit at 20 ma
0 - 100
%
DMT20MA
100
Loadshed Group Number
0 - 99
SHED_NUM
0
Loadshed Demand Delta
0 - 60
%
SHED_DEL
0
Maximum Loadshed Time
0 - 120
min
SHED_TIM
60
Demand Limit Sw.1 Setpt.
0 - 100
%
DLSWSP1
80
Demand Limit Sw.2 Setpt.
0 - 100
%
DLSWSP2
50
ECON
Economizer Installed ?
Yes/No
ECON_ENA
Yes
Economizer Min.Position
0 - 100
%
ECONOMIN
20
Economizer Max.Position
0 - 100
%
ECONOMAX
98
Economzr trim for sumZ ?
Yes/No
ECONTRIM
Yes
Econ ChangeOver Select
0 - 3
ECON_SEL
1
OA Enthalpy ChgOvr Selct
1 - 5
OAEC_SEL
2
Outdr.Enth Compare Value
18 - 28
OAEN_CFG
24
High OAT Lockout Temp
55 - 120
dF
OAT_LOCK
60
OA Dewpoint Temp Limit
50 - 62
dF
OADEWCFG
55
Outside Air RH Sensor
Enable/Disable
OARHSENS
Disable
Economizer Control Type
1-3
ECON_CTL
1
Economizer Switch Config
0-2
ECOSWCFG
0
Economizer Prop.Gain
0.7 - 3.0
EC_PGAIN
1
Economizer Range Adjust
0.5 - 5
^F
EC_RANGE
2.5
Economizer Speed Adjust
0.1 - 10
EC_SPEED
0.75
Economizer Deadband
0.1 - 2
^F
EC_DBAND
0.5
Unoc Econ Free Cool Cfg
0-2
UEFC_CFG
0
Unoc Econ Free Cool Time
0-720
min
UEFCTIME
120
Un.Ec.Free Cool OAT Lock
40-70
dF
UEFCNTLO
50
EDTR
EDT Reset Configuration
0 - 3
EDRSTCFG
0
Reset Ratio
0 - 10
RTIO
2
Reset Limit
0 - 20
^F
LIMT
10
EDT 4-20 ma Reset Input
Enable/Disable
EDTRSENS
Disable
Summary of Contents for WEATHERMAKER 48/50AJ
Page 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Page 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Page 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Page 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Page 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Page 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Page 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Page 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Page 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Page 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...