151
APPENDIX B — CCN TABLES (cont)
SET POINT TABLE
CONFIG TABLES
TABLE
NAME
RANGE
UNITS
POINT NAME
DEFAULT
SET_PNT
Occupied Heat Setpoint
40-99
dF
OHSP
68
Occupied Cool Setpoint
40-99
dF
OCSP
75
Unoccupied Heat Setpoint
40-99
dF
UHSP
55
Unoccupied Cool Setpoint
40-99
dF
UCSP
90
Heat-Cool Setpoint Gap
2-10
^F
HCSP_GAP
5
VAV Occ. Cool On Delta
0-25
^F
VAVOCON
3.5
VAV Occ. Cool Off Delta
1-25
^F
VAVOCOFF
2
Supply Air Setpoint
45-75
dF
SASP
55
Supply Air Setpoint Hi
45-75
dF
SASP_HI
55
Supply Air Setpoint Lo
45-75
dF
SASP_LO
60
Heating Supply Air Setpt
80-100
dF
SASPHEAT
85
Tempering Purge SASP
–20-80
dF
TEMPPURG
50
Tempering in Cool SASP
5-75
dF
TEMPCOOL
5
Tempering in Vent Occ SASP
–20-80
dF
TEMPVOCC
65
Tempering Vent Unocc. SASP
–20-80
dF
TEMPVUNC
50
TABLE
NAME
RANGE
UNITS
POINT NAME
DEFAULT
ALARMDEF
Alarm Routing Control
00000000-11111111
ALRM_CNT
11000000
Equipment Priority
0 - 7
EQP_TYPE
5
Comm Failure Retry Time
1 - 240
min
RETRY_TM
10
Re-Alarm Time
1 - 255
min
RE-ALARM
30
Alarm System Name
up to 8 alphanum
ALRM_NAM
A-SERIES
BRODEFS
CCN Time/Date Broadcast
Off/On
CCNBC
Off
CCN OAT Broadcast
Off/On
OATBC
Off
CCN OARH Broadcast
Off/On
OARHBC
Off
CCN OAQ Broadcast
Off/On
OAQBC
Off
Global Schedule Broadcst
Off/On
GSBC
Off
Daylight Savings Start:
Month
1 - 12
STARTM
4
Week
1 - 5
STARTW
1
Day
1 - 7
STARTD
7
Minutes to Add
0 - 90
MINADD
60
Daylight Savings Stop:
Month
1 - 12
STOPM
10
Week
1 - 5
STOPW
5
Day
1 - 7
STOPD
7
Minutes to Subtract
0 - 90
MINSUB
60
Ctlr-ID
Device Name:
A-Series
Description:
A Series Rooftop
Location:
Software Part Number:
CESR131343-XX-XX
Model Number:
Serial Number:
Reference Number:
HOLIDAY
Broadcast Supervisory
HOLDY01S
Holiday Start Month
1-12
HOL-MON
0
to
Start Day
1-31
HOL-DAY
0
HOLDY30S
Duration (days)
1-99
HOL-LEN
0
OCCDEFCS
Occupancy Supervisory
Timed Override Hours
0
OVR-EXT
Period 1 DOW (MTWTFSSH)
00000000
DOW1
Occupied From
0:00
OCCTOD1
Occupied To
0:00
UNOCTOD1
Period 2 DOW (MTWTFSSH)
00000000
DOW2
Occupied From
0:00
OCCTOD2
Occupied To
0:00
UNOCTOD2
Period 3 DOW (MTWTFSSH)
00000000
DOW3
Occupied From
0:00
OCCTOD3
Occupied To
0:00
UNOCTOD3
Period 4 DOW (MTWTFSSH)
00000000
DOW4
Occupied From
0:00
OCCTOD4
Occupied To
0:00
UNOCTOD4
Period 5 DOW (MTWTFSSH)
00000000
DOW5
Occupied From
0:00
OCCTOD5
Occupied To
0:00
UNOCTOD5
Period 6 DOW (MTWTFSSH)
00000000
DOW6
Occupied From
0:00
OCCTOD6
Occupied To
0:00
UNOCTOD6
Period 7 DOW (MTWTFSSH)
00000000
DOW7
Occupied From
0:00
OCCTOD7
Occupied To
0:00
UNOCTOD7
Period 8 DOW (MTWTFSSH)
00000000
DOW8
Occupied From
0:00
OCCTOD8
Occupied To
0:00
UNOCTOD8
Summary of Contents for WEATHERMAKER 48/50AJ
Page 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Page 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Page 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Page 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Page 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Page 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Page 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Page 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Page 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Page 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...