APPENDIX C — VFD INFORMATION
On variable air volume units with optional VFD, the supply
fan speed is controlled by a 3-phase VFD. The VFD is located
in the supply fan section behind a removable panel. The VFD
speed is controlled directly by the
Comfort
Link™ controls
through a 4 to 20 mA signal based on a supply duct pressure
sensor. The VFD has a display, which can be used for service
diagnostics, but setup of the building pressure and control loop
factors should be done through the scrolling marquee display.
The VFD is powered during normal operation to prevent
condensation from forming on the boards during the off mode
and is stopped by driving the speed to 0 (by sending a 4 mA
signal to the VFD).
The A Series units use ABB VFDs. The interface wiring for
the VFDs is shown in Fig. A. The VFD connects through
an isolation board to the 4 to 20 mA RCB board. Terminal
designations are shown in Table A. Configurations are shown
in Table B.
Table A — VFD Terminal Designations
TERMINAL
FUNCTION
U1
V1
W1
Three-Phase Main Circuit Input Power Supply
U2
V2
Three-Phase AC Output to Motor, 0 V to
W2
Maximum Input Voltage Level
X1-11 (GND)
X1-12 (COMMON)
Factory-supplied jumper
X1-10 (24 VDC)
X1-13 (DI-1)
Run (factory-supplied jumper)
X1-10 (24 VDC)
Start Enable 1 (Factory-supplied jumper). When
X1-16 (DI-4)
opened the drive goes to emergency stop.
X1-2 (AI-1)
X1-3 (AGND)
Factory wired for 4 to 20 mA remote input
Fig. A — VFD Wiring
A48-7712
Summary of Contents for WEATHERMAKER 48/50AJ
Page 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Page 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Page 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Page 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Page 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Page 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Page 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Page 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Page 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Page 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...