19

In either case, the bypass controller will check to ensure the

fan is off by reading its pressure sensor and damper position. If
the pressure reading is less than 10% of the static pressure set
point and the bypass damper position is less than 25% of the
resistance of the feedback potentiometer for greater than
60 seconds, then the bypass controller assumes the fan is off.
When the fan is off, the bypass controller will drive its damper
to the fully open position. If an invalid feedback resistance
value is detected, the bypass controller will terminate the
calibration. Once at the fully open damper position, the bypass
controller will read the output voltage of the pressure sensor. If

the voltage reads within the range of 1.0 vdc ± 0.1 volt, it
calculates the offset voltage based on the difference between
the output voltage reading and the nominal zero pressure
reading of 1.0 vdc. This value is then stored in non-volatile
memory. If the voltage reading is outside of the tolerance
range, the bypass controller will display “Alarm” in the
commissioning screen. The screen will display “Alarm” until a
successful calibration of the pressure sensor is performed.
When the calibration is completed, the bypass controller will
signal the Linkage Coordinator to return the fan to normal
operation.

Summary of Contents for VVT 33ZC

Page 1: ...oordinate up to 31 additional zone controllers The purpose of the Linkage Coordinator zone relationship is to provide an efficient data path for communica tion between the zone controllers bypass cont...

Page 2: ...ding the damper shaft through the actuator clamp assembly See Fig 2 for details Remove the controller wiring access cover Secure the controller by installing the screw provided through the grommet in...

Page 3: ...3 Fig 2 Bypass Controller Dimensions Fig 1 Bypass Controller Details...

Page 4: ...ENSOR 1 6 J5 3 1 G CCN 3 3 G 1 1 5 1 6 1 J4 1 2 NOT USED NOT USED NOT USED DAT NOT USED NOT USED NOT USED NOT USED DAT TO COMMUNICATION BUS TO FEEDBACK POTENTIOMETER LINE VOLTAGE EQUIPMENT GROUND TO D...

Page 5: ...p the grommet into the hole until it is secure Pull on the leads of the duct sensor until the sensor is snug against the grommet 3 Connect the sensor leads to the bypass controller s termi nal board a...

Page 6: ...reverse rotation the actuator switch may be changed to the CCW position LINKED ACTUATORS Field supplied linked actuators may be used to link to the bypass controller actuator Install the actuators pe...

Page 7: ...7 Fig 7 High Torque Actuator Wiring...

Page 8: ...8 Fig 8 High Torque Actuator with Linked Dampers Wiring...

Page 9: ...9 Fig 9 Field Supplied Linked Damper Wiring...

Page 10: ...10 Fig 10 Multiple Field Supplied Linked Damper Wiring...

Page 11: ...s cable a color code system for the entire network is recommended to simplify installation and checkout See Table 4 for the recommended color code Table 4 Color Code Recommendations 3 Connect the othe...

Page 12: ...ew bypass pressure set point 10 Read the airflow with a measuring device If the reading varies from the screen value force the value to the mea sured value Once the pressure sensor is forced the contr...

Page 13: ...iable displays whether the leaving air temperature exceeds the heating or cooling limit configured in the Bypass Controller Service Configuration Table If Yes is displayed the System Pressure Set Poin...

Page 14: ...zone controller to turn the system fan off If the communication fails the damper calibration process will be terminated and this decision will be Disabled When the fan is off the zone controller will...

Page 15: ...NT Duct Temperature This variable displays the duct tempera ture at the bypass damper through a 10K thermistor with a measurement range from 40 to 245 F in 0 1 F increments Duct Temperature Display Un...

Page 16: ...efault Value Close Max Damper Alarm Limit This decision is used to gener ate alarms during system heating and cooling modes When the bypass damper position is greater than this configured limit and th...

Page 17: ...ease to within the zero tolerance 1 0 0 1 vdc of the sensor The alarm is disabled if this decision is set to Disable Press Sensr Cal Alarm Default Value Enable Display Range Enable Disable Duct Temp C...

Page 18: ...is off When the fan is off the bypass controller will drive its damper to the fully closed position The bypass controller will read the value of the actuator s feedback potentiometer until the value...

Page 19: ...l terminate the calibration Once at the fully open damper position the bypass controller will read the output voltage of the pressure sensor If the voltage reads within the range of 1 0 vdc 0 1 volt i...

Page 20: ...b 11a 13a Copyright 2004 Carrier Corporation SEN Fig 12 Bypass Controller Operation Flow Chart LEGEND BP Bypass BP_SETPT System Pressure Setpoint DAT Duct Air Temperature DMP_POS Damper Position LAT L...

Reviews: