Maintenance Tables —

The bypass controller contains

the following maintenance tables, Bypass Controller Mainte-
nance Table (BP_MAINT), Bypass Controller Commissioning
Maintenance Table (BPCOMMIS), and Bypass Controller Sys-
tem Pilot Default Maintenance (SP_MAINT).
BYPASS CONTROLLER MAINTENANCE TABLE —
See Table 6 for Bypass Controller Maintenance Table
(BP_MAINT).
System Mode — This variable displays the master zone con-
troller’s system mode as the bypass controller’s system mode
except when the bypass controller is in its commissioning
mode or the network communication fails. In bypass commis-
sioning mode, the system mode will display

BPCOMMIS

to

indicate the bypass controller is in its own commissioning
mode. If the network communication between the bypass
controller and the master zone controller fails, the system mode
will display

LOCAL

.

System Mode:

Display Units

ASCII

Display Range

HEATING, COOLING,
FREE COOL,
PRESSURE,
EVAC, ZONE_BAL,
OFF, BPCOMMIS,
LOCAL

Forcible

No

Damper Position — This variable displays the damper posi-
tion percent range of rotation determined by the damper feed-
back potentiometer. The bypass controller is designed for use
on dampers with a range of rotation up to 90 degrees.
Damper
Position:

Display Units

% open

Display Range

0 to 100

Forcible

No

System Pressure Setpt — This variable displays the supply air
static pressure set point that is to be maintained by the bypass
controller. The bypass controller determines the damper posi-
tion by comparing the system static pressure to this set point.
System Pressure
Setpoint:

Display Units

in. wg

Display Range

0.10 to 1.80

Forcible

No

LAT Exceeds Limit — This variable displays whether the
leaving air temperature exceeds the heating or cooling limit
configured in the Bypass Controller Service Configuration
Table. If

Yes

is displayed, the System Pressure Set Point is

increased by the value in LAT Pressure Delta. This will cause
the amount of bypassed air to be reduced, thus protecting the
air source from receiving air that is too hot or too cool. If No is
displayed, then no LAT protection is in effect.
LAT Exceeds
Limit:

Default Value

No

Display Range

Yes/No

Forcible

No

LAT Pressure Delta — This variable displays the amount of
in. wg by which the System Pressure Set Point will be in-
creased if LAT Exceeds Limit displays Yes.
LAT Pressure
Delta:

Display Units

in. wg

Display Range

0.00 to 1.00

Forcible

No

System Pressure — This variable displays the static system
pressure through an integrated pressure sensor in increments of
0.1 in. wg.

System Pressure: Display Units

in. wg

Display Range

0.00 to 2.00

Forcible

No

Duct Temperature — This variable displays the duct tempera-
ture at the bypass damper through a 10K thermistor with a
measurement range from –40 to 245 F in 0.1° F increments.
Duct
Temperature:

Display Units

F (C)

Display Range

–40.0 to 245.0

Forcible

Yes

Clear Alarms — This variable displays the commanded state
of the Clear Alarms function. If this decision is forced to

Yes

,

all alarms in the Alarm History Table will be cleared and this
decision will automatically be set back to

No

.

Clear
Alarms:

Default Value

No

Display Range

Yes/No

Forcible

Yes

Table 6 — Maintenance

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

System Mode

BPCOMMIS

SYS_MODE

Damper Position

58

%OPEN

DMP_POS

System Pressure Setpt

1.50

in H2O

SP_SETPT

LAT Exceeds Limit

No

LAT_ALRM

LAT Pressure Delta

0.00

in H2O

DELTA_SP

System Pressure

0.00

in H2O

SP_SENSR

Duct Temperature

73.8

dF

DUCT_TMP

Clear Alarms

No

CLR_ALRM

Summary of Contents for VVT 33ZC

Page 1: ...oordinate up to 31 additional zone controllers The purpose of the Linkage Coordinator zone relationship is to provide an efficient data path for communica tion between the zone controllers bypass cont...

Page 2: ...ding the damper shaft through the actuator clamp assembly See Fig 2 for details Remove the controller wiring access cover Secure the controller by installing the screw provided through the grommet in...

Page 3: ...3 Fig 2 Bypass Controller Dimensions Fig 1 Bypass Controller Details...

Page 4: ...ENSOR 1 6 J5 3 1 G CCN 3 3 G 1 1 5 1 6 1 J4 1 2 NOT USED NOT USED NOT USED DAT NOT USED NOT USED NOT USED NOT USED DAT TO COMMUNICATION BUS TO FEEDBACK POTENTIOMETER LINE VOLTAGE EQUIPMENT GROUND TO D...

Page 5: ...p the grommet into the hole until it is secure Pull on the leads of the duct sensor until the sensor is snug against the grommet 3 Connect the sensor leads to the bypass controller s termi nal board a...

Page 6: ...reverse rotation the actuator switch may be changed to the CCW position LINKED ACTUATORS Field supplied linked actuators may be used to link to the bypass controller actuator Install the actuators pe...

Page 7: ...7 Fig 7 High Torque Actuator Wiring...

Page 8: ...8 Fig 8 High Torque Actuator with Linked Dampers Wiring...

Page 9: ...9 Fig 9 Field Supplied Linked Damper Wiring...

Page 10: ...10 Fig 10 Multiple Field Supplied Linked Damper Wiring...

Page 11: ...s cable a color code system for the entire network is recommended to simplify installation and checkout See Table 4 for the recommended color code Table 4 Color Code Recommendations 3 Connect the othe...

Page 12: ...ew bypass pressure set point 10 Read the airflow with a measuring device If the reading varies from the screen value force the value to the mea sured value Once the pressure sensor is forced the contr...

Page 13: ...iable displays whether the leaving air temperature exceeds the heating or cooling limit configured in the Bypass Controller Service Configuration Table If Yes is displayed the System Pressure Set Poin...

Page 14: ...zone controller to turn the system fan off If the communication fails the damper calibration process will be terminated and this decision will be Disabled When the fan is off the zone controller will...

Page 15: ...NT Duct Temperature This variable displays the duct tempera ture at the bypass damper through a 10K thermistor with a measurement range from 40 to 245 F in 0 1 F increments Duct Temperature Display Un...

Page 16: ...efault Value Close Max Damper Alarm Limit This decision is used to gener ate alarms during system heating and cooling modes When the bypass damper position is greater than this configured limit and th...

Page 17: ...ease to within the zero tolerance 1 0 0 1 vdc of the sensor The alarm is disabled if this decision is set to Disable Press Sensr Cal Alarm Default Value Enable Display Range Enable Disable Duct Temp C...

Page 18: ...is off When the fan is off the bypass controller will drive its damper to the fully closed position The bypass controller will read the value of the actuator s feedback potentiometer until the value...

Page 19: ...l terminate the calibration Once at the fully open damper position the bypass controller will read the output voltage of the pressure sensor If the voltage reads within the range of 1 0 vdc 0 1 volt i...

Page 20: ...b 11a 13a Copyright 2004 Carrier Corporation SEN Fig 12 Bypass Controller Operation Flow Chart LEGEND BP Bypass BP_SETPT System Pressure Setpoint DAT Duct Air Temperature DMP_POS Damper Position LAT L...

Reviews: