background image

5

Bypass Controller Inputs and Outputs —

The by-

pass controller inputs and outputs are shown in Tables 1
and 2.

Table 1 — Bypass Controller Inputs

Table 2 — Bypass Controller Outputs

Install Duct Temperature Sensor —

The duct tem-

perature sensor is required. The duct temperature sensor must
be installed in the supply air duct. The 33ZCSENDAT is the
recommended sensor. See Fig. 5 for sensor details.

For bypass systems, the duct temperature sensor should be

moved to a location which will provide the best sensing of the
supply-air temperature during heating and cooling.

For bypass systems using a ducted supply, the duct tempera-

ture sensor should be located in the main supply duct
downstream of the discharge of the air source and before the
bypass damper to allow good mixing of the supply airstream.

The 33ZCSENDAT duct sensor is a small epoxy sensor that

is 1

1

/

4

-in. long. A grommet is provided for filling the hole

around the sensor cable after the sensor is located in the duct.

See Fig. 3 and 6 for mounting location.

Do not run sensor or relay wires in the same conduit or race-

way with Class 1 AC service wiring. Do not abrade, cut, or
nick the outer jacket of the cable. Do not pull or draw cable
with a force that may harm the physical or electrical properties.
Avoid splices in any control wiring.

Perform the following steps to connect the duct temperature

sensor to the bypass controller:

1. Drill or punch a

1

/

4

-in. hole in the supply duct. See

Fig. 6. Duct sensor can be installed to hang from top of
duct or from the sides. Sensor probe can touch side of
duct.

2. Push sensor through hole in the supply duct. Snap the

grommet into the hole until it is secure. Pull on the leads
of the duct sensor until the sensor is snug against the
grommet.

3. Connect the sensor leads to the bypass controller’s termi-

nal board at the terminals labeled DAT (J4-10) and GND
(J4-12). See Fig. 4 for wiring. If extending cable length
beyond 8 ft, use plenum rated, 20 AWG (American Wire
Gage), twisted pair wire. Sensor wiring does not have
polarity. Either lead can be wired to either terminal.

4. Neatly bundle and secure excess wire.
5. Using electrical tape, insulate any exposed lead to prevent

shorting.

6. Connect shield to earth ground (if shielded wire is used).

Install Pressure Tubing —

The static pressure pick up

should be located in the main supply duct before the first
branching of ductwork. Run the tubing from the bypass con-
troller to the installation location. For stable airflow measure-
ment, the recommended minimum length of tubing is 2 ft.
Connect the tubing to the high side of the pressure sensor
marked P1. Make sure the low side of the pressure sensor (P2)
is open to the atmosphere. See Fig. 3.

CHANNEL

J4 TERMINATIONS

DESCRIPTION

CONTROL

DEVICE

DUCT_TMP

10, 12

Duct Temperature

10K Thermistor

DMP_POS

9 (10 v), 7 (W+), 5 (–)

Damper Position

0-10 VDC

SP_SENSR

3, 1

System Pressure

0-5 VDC

CHANNEL

J5 TERMINATIONS

DESCRIPTION

CONTROL

DEVICE

DMPR_CCW

1 (24 VAC), 2

Damper CCW

24 VAC

DMPR_CW

3 (24 VAC), 2

Damper CW

24 VAC

Disconnect electrical power before wiring the bypass con-
troller. Electrical shock, personal injury, or damage to the
fan coil controller can result.

.225/ .245
(5.72/6.22)

75.0

.5

(1905)

1.00

(25.4)

1.25

(31.8)

0.06

(1.5)

Fig. 5 — 33ZCSENDAT Duct Sensor

NOTE: Dimensions are in inches.
Dimensions in ( ) are in mm.

DRILL 1/4" HOLE
IN TOP OF DUCT
AND LET SENSOR
HANG DOWN

ALTERNATE INSTALLATION
LOCATION INSIDE OF DUCT

SUPPLY DUCT

Fig. 6 — DAT Installation Location

Summary of Contents for VVT 33ZC

Page 1: ...oordinate up to 31 additional zone controllers The purpose of the Linkage Coordinator zone relationship is to provide an efficient data path for communica tion between the zone controllers bypass cont...

Page 2: ...ding the damper shaft through the actuator clamp assembly See Fig 2 for details Remove the controller wiring access cover Secure the controller by installing the screw provided through the grommet in...

Page 3: ...3 Fig 2 Bypass Controller Dimensions Fig 1 Bypass Controller Details...

Page 4: ...ENSOR 1 6 J5 3 1 G CCN 3 3 G 1 1 5 1 6 1 J4 1 2 NOT USED NOT USED NOT USED DAT NOT USED NOT USED NOT USED NOT USED DAT TO COMMUNICATION BUS TO FEEDBACK POTENTIOMETER LINE VOLTAGE EQUIPMENT GROUND TO D...

Page 5: ...p the grommet into the hole until it is secure Pull on the leads of the duct sensor until the sensor is snug against the grommet 3 Connect the sensor leads to the bypass controller s termi nal board a...

Page 6: ...reverse rotation the actuator switch may be changed to the CCW position LINKED ACTUATORS Field supplied linked actuators may be used to link to the bypass controller actuator Install the actuators pe...

Page 7: ...7 Fig 7 High Torque Actuator Wiring...

Page 8: ...8 Fig 8 High Torque Actuator with Linked Dampers Wiring...

Page 9: ...9 Fig 9 Field Supplied Linked Damper Wiring...

Page 10: ...10 Fig 10 Multiple Field Supplied Linked Damper Wiring...

Page 11: ...s cable a color code system for the entire network is recommended to simplify installation and checkout See Table 4 for the recommended color code Table 4 Color Code Recommendations 3 Connect the othe...

Page 12: ...ew bypass pressure set point 10 Read the airflow with a measuring device If the reading varies from the screen value force the value to the mea sured value Once the pressure sensor is forced the contr...

Page 13: ...iable displays whether the leaving air temperature exceeds the heating or cooling limit configured in the Bypass Controller Service Configuration Table If Yes is displayed the System Pressure Set Poin...

Page 14: ...zone controller to turn the system fan off If the communication fails the damper calibration process will be terminated and this decision will be Disabled When the fan is off the zone controller will...

Page 15: ...NT Duct Temperature This variable displays the duct tempera ture at the bypass damper through a 10K thermistor with a measurement range from 40 to 245 F in 0 1 F increments Duct Temperature Display Un...

Page 16: ...efault Value Close Max Damper Alarm Limit This decision is used to gener ate alarms during system heating and cooling modes When the bypass damper position is greater than this configured limit and th...

Page 17: ...ease to within the zero tolerance 1 0 0 1 vdc of the sensor The alarm is disabled if this decision is set to Disable Press Sensr Cal Alarm Default Value Enable Display Range Enable Disable Duct Temp C...

Page 18: ...is off When the fan is off the bypass controller will drive its damper to the fully closed position The bypass controller will read the value of the actuator s feedback potentiometer until the value...

Page 19: ...l terminate the calibration Once at the fully open damper position the bypass controller will read the output voltage of the pressure sensor If the voltage reads within the range of 1 0 vdc 0 1 volt i...

Page 20: ...b 11a 13a Copyright 2004 Carrier Corporation SEN Fig 12 Bypass Controller Operation Flow Chart LEGEND BP Bypass BP_SETPT System Pressure Setpoint DAT Duct Air Temperature DMP_POS Damper Position LAT L...

Reviews: