BYPASS CONTROLLER COMMISSIONING MAINTE-
NANCE TABLE — See Table 7 for Bypass Controller Com-
missioning Maintenance Table (BPCOMMIS).
Bypass Commis (60 min) — This variable displays whether
the bypass commissioning function has been enabled. The by-
pass commissioning function permits the user to calibrate the
bypass damper and the system pressure sensor. All calibration
decisions will remain disabled until the user forces Bypass
Commissioning to

Enable

. When the user forces this decision

to

Enable

, System Mode will be updated to

BPCOMMIS

to in-

dicate that bypass commissioning is in effect.

Bypass controller commissioning will automatically be dis-

abled if no activity is detected in the commissioning mainte-
nance table (for example, if none of the calibration decisions
are forced or if communication with the zone controller is lost)
for one hour.
Bypass
Commiss:

Default Value

Disable

Display Range

Enable/Disable

Forcible

Yes

Damper Calibration — This variable displays whether the
damper calibration process has been enabled. When the user
forces this decision to

Enable

after Bypass Commissioning has

also been forced to

Enable

, the bypass damper is calibrated.

If the system fan is on, the bypass controller sends a request

to the Linkage Coordinator zone controller to turn the system
fan off. If the communication fails, the damper calibration pro-
cess will be terminated and this decision will be

Disabled

.

When the fan is off, the zone controller will drive the damp-

er to the full closed position.

After completing the closed position calibration, the zone

controller will drive the damper to the full open position.

If there was an error during the closed or open position cali-

bration, an alarm will be generated and Damper Cal Alarm will
display

Alarm

until a successful damper calibration takes place.

When calibration is completed, the force will be removed

from Damper Calibration decision, and the bypass controller
will send a request to the Linkage Coordinator zone controller
to return the system fan to normal operation. The damper will
remain fully open.
NOTE: Bypass controller commissioning will automatically
be disabled if no activity is detected in this maintenance table
for one hour.
Damper
Calibration:

Default Value

Disable

Display Range

Enable/Disable

Forcible

Yes

Zero Pressure Cal — This variable displays whether the pres-
sure transducer zero calibration process has been enabled.
When the user forces this decision to

Enable

after Bypass

Commissioning has also been set to

Enable

, the pressure trans-

ducer is calibrated.

If the system fan is on, the zone controller will send a re-

quest to the Linkage Coordinator zone controller to turn the

system fan off. If the communication fails, the damper
calibration process will be terminated and this decision will be

Disabled

.

When the fan is off, the zone controller will drive the damp-

er to the full open position.

The bypass controller will measure the output voltage of the

pressure sensor and verify that the output voltage is within the
tolerance of zero pressure voltage of the sensor (1.0 ± 0.1 vdc).

If the pressure sensor voltage failed to decrease to within the

zero pressure tolerance (1.0 ± 0.1 vdc), a Press Sensr Cal
Alarm will be displayed until a successful calibration takes
place.

When calibration is completed, the force is removed from

Zero Pressure Cal decision, and the bypass controller will send
a request to the Linkage Coordinator zone controller to return
the system fan to normal operation. The damper will remain
fully open.
NOTE: This value cannot be forced if Auto Press Cal is set to

Enable

in the Sensor Service Configuration Table.

NOTE: Bypass Controller Commissioning will automatically
be disabled if no activity is detected in this maintenance table
for one hour.
Zero Pressure
Cal:

Default Value

Disable

Display Range

Enable/Disable

Forcible

Yes

Pressure Sensor Cal — This variable displays whether the
high-end pressure transducer calibration process has been
enabled. The purpose of this process is to correctly calibrate the
pressure transducer. When the user forces this decision to

Enable

after Bypass Commissioning has also been set to

Enable

, the user may then force the System Pressure to the

correct reading as measured with calibrated test equipment.
From the forced value, the bypass controller calculates a cali-
bration multiplier that will always be applied to the System
Pressure sensor reading. Once the multiplier is calculated, the
force is removed and the multiplier is applied to the System
Pressure sensor reading.
NOTE: Bypass controller commissioning will automatically
be disabled if no activity is detected in this maintenance table
for one hour.
Pressure
Sensor Cal:

Default Value

Disable

Display Range

Enable/Disable

Forcible

Yes

Damper Position — This variable displays the damper posi-
tion percent range of rotation determined by the damper feed-
back potentiometer. The bypass controller is designed for use
on dampers with a range of rotation up to 90 degrees.
Damper
Position:

Display Units

% open

Default Value

0

Display Range

0 to 100

Forcible

No

Table 7 — Commissioning Maintenance

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

Bypass Commis (60 min)

Enable

Service

COMMISS

Damper Calibration

Disable

DMP_CAL

Zero Pressure Cal

Disable

ZR_PSCAL

Pressure Sensor Cal

Disable

PS_CAL

Damper Position

42

%OPEN

DMP_POS

System Pressure

0.00

in H2O

SP_SENSR

System Pressure Setpt

1.50

in H2O

SP_SETPT

Damper Cal Alarm

Normal

DAMP_CAL

Press Sensr Cal Alarm

Normal

SP_CAL

Summary of Contents for VVT 33ZC

Page 1: ...oordinate up to 31 additional zone controllers The purpose of the Linkage Coordinator zone relationship is to provide an efficient data path for communica tion between the zone controllers bypass cont...

Page 2: ...ding the damper shaft through the actuator clamp assembly See Fig 2 for details Remove the controller wiring access cover Secure the controller by installing the screw provided through the grommet in...

Page 3: ...3 Fig 2 Bypass Controller Dimensions Fig 1 Bypass Controller Details...

Page 4: ...ENSOR 1 6 J5 3 1 G CCN 3 3 G 1 1 5 1 6 1 J4 1 2 NOT USED NOT USED NOT USED DAT NOT USED NOT USED NOT USED NOT USED DAT TO COMMUNICATION BUS TO FEEDBACK POTENTIOMETER LINE VOLTAGE EQUIPMENT GROUND TO D...

Page 5: ...p the grommet into the hole until it is secure Pull on the leads of the duct sensor until the sensor is snug against the grommet 3 Connect the sensor leads to the bypass controller s termi nal board a...

Page 6: ...reverse rotation the actuator switch may be changed to the CCW position LINKED ACTUATORS Field supplied linked actuators may be used to link to the bypass controller actuator Install the actuators pe...

Page 7: ...7 Fig 7 High Torque Actuator Wiring...

Page 8: ...8 Fig 8 High Torque Actuator with Linked Dampers Wiring...

Page 9: ...9 Fig 9 Field Supplied Linked Damper Wiring...

Page 10: ...10 Fig 10 Multiple Field Supplied Linked Damper Wiring...

Page 11: ...s cable a color code system for the entire network is recommended to simplify installation and checkout See Table 4 for the recommended color code Table 4 Color Code Recommendations 3 Connect the othe...

Page 12: ...ew bypass pressure set point 10 Read the airflow with a measuring device If the reading varies from the screen value force the value to the mea sured value Once the pressure sensor is forced the contr...

Page 13: ...iable displays whether the leaving air temperature exceeds the heating or cooling limit configured in the Bypass Controller Service Configuration Table If Yes is displayed the System Pressure Set Poin...

Page 14: ...zone controller to turn the system fan off If the communication fails the damper calibration process will be terminated and this decision will be Disabled When the fan is off the zone controller will...

Page 15: ...NT Duct Temperature This variable displays the duct tempera ture at the bypass damper through a 10K thermistor with a measurement range from 40 to 245 F in 0 1 F increments Duct Temperature Display Un...

Page 16: ...efault Value Close Max Damper Alarm Limit This decision is used to gener ate alarms during system heating and cooling modes When the bypass damper position is greater than this configured limit and th...

Page 17: ...ease to within the zero tolerance 1 0 0 1 vdc of the sensor The alarm is disabled if this decision is set to Disable Press Sensr Cal Alarm Default Value Enable Display Range Enable Disable Duct Temp C...

Page 18: ...is off When the fan is off the bypass controller will drive its damper to the fully closed position The bypass controller will read the value of the actuator s feedback potentiometer until the value...

Page 19: ...l terminate the calibration Once at the fully open damper position the bypass controller will read the output voltage of the pressure sensor If the voltage reads within the range of 1 0 vdc 0 1 volt i...

Page 20: ...b 11a 13a Copyright 2004 Carrier Corporation SEN Fig 12 Bypass Controller Operation Flow Chart LEGEND BP Bypass BP_SETPT System Pressure Setpoint DAT Duct Air Temperature DMP_POS Damper Position LAT L...

Reviews: