14
BYPASS CONTROLLER COMMISSIONING MAINTE-
NANCE TABLE — See Table 7 for Bypass Controller Com-
missioning Maintenance Table (BPCOMMIS).
Bypass Commis (60 min) — This variable displays whether
the bypass commissioning function has been enabled. The by-
pass commissioning function permits the user to calibrate the
bypass damper and the system pressure sensor. All calibration
decisions will remain disabled until the user forces Bypass
Commissioning to
Enable
. When the user forces this decision
to
Enable
, System Mode will be updated to
BPCOMMIS
to in-
dicate that bypass commissioning is in effect.
Bypass controller commissioning will automatically be dis-
abled if no activity is detected in the commissioning mainte-
nance table (for example, if none of the calibration decisions
are forced or if communication with the zone controller is lost)
for one hour.
Bypass
Commiss:
Default Value
Disable
Display Range
Enable/Disable
Forcible
Yes
Damper Calibration — This variable displays whether the
damper calibration process has been enabled. When the user
forces this decision to
Enable
after Bypass Commissioning has
also been forced to
Enable
, the bypass damper is calibrated.
If the system fan is on, the bypass controller sends a request
to the Linkage Coordinator zone controller to turn the system
fan off. If the communication fails, the damper calibration pro-
cess will be terminated and this decision will be
Disabled
.
When the fan is off, the zone controller will drive the damp-
er to the full closed position.
After completing the closed position calibration, the zone
controller will drive the damper to the full open position.
If there was an error during the closed or open position cali-
bration, an alarm will be generated and Damper Cal Alarm will
display
Alarm
until a successful damper calibration takes place.
When calibration is completed, the force will be removed
from Damper Calibration decision, and the bypass controller
will send a request to the Linkage Coordinator zone controller
to return the system fan to normal operation. The damper will
remain fully open.
NOTE: Bypass controller commissioning will automatically
be disabled if no activity is detected in this maintenance table
for one hour.
Damper
Calibration:
Default Value
Disable
Display Range
Enable/Disable
Forcible
Yes
Zero Pressure Cal — This variable displays whether the pres-
sure transducer zero calibration process has been enabled.
When the user forces this decision to
Enable
after Bypass
Commissioning has also been set to
Enable
, the pressure trans-
ducer is calibrated.
If the system fan is on, the zone controller will send a re-
quest to the Linkage Coordinator zone controller to turn the
system fan off. If the communication fails, the damper
calibration process will be terminated and this decision will be
Disabled
.
When the fan is off, the zone controller will drive the damp-
er to the full open position.
The bypass controller will measure the output voltage of the
pressure sensor and verify that the output voltage is within the
tolerance of zero pressure voltage of the sensor (1.0 ± 0.1 vdc).
If the pressure sensor voltage failed to decrease to within the
zero pressure tolerance (1.0 ± 0.1 vdc), a Press Sensr Cal
Alarm will be displayed until a successful calibration takes
place.
When calibration is completed, the force is removed from
Zero Pressure Cal decision, and the bypass controller will send
a request to the Linkage Coordinator zone controller to return
the system fan to normal operation. The damper will remain
fully open.
NOTE: This value cannot be forced if Auto Press Cal is set to
Enable
in the Sensor Service Configuration Table.
NOTE: Bypass Controller Commissioning will automatically
be disabled if no activity is detected in this maintenance table
for one hour.
Zero Pressure
Cal:
Default Value
Disable
Display Range
Enable/Disable
Forcible
Yes
Pressure Sensor Cal — This variable displays whether the
high-end pressure transducer calibration process has been
enabled. The purpose of this process is to correctly calibrate the
pressure transducer. When the user forces this decision to
Enable
after Bypass Commissioning has also been set to
Enable
, the user may then force the System Pressure to the
correct reading as measured with calibrated test equipment.
From the forced value, the bypass controller calculates a cali-
bration multiplier that will always be applied to the System
Pressure sensor reading. Once the multiplier is calculated, the
force is removed and the multiplier is applied to the System
Pressure sensor reading.
NOTE: Bypass controller commissioning will automatically
be disabled if no activity is detected in this maintenance table
for one hour.
Pressure
Sensor Cal:
Default Value
Disable
Display Range
Enable/Disable
Forcible
Yes
Damper Position — This variable displays the damper posi-
tion percent range of rotation determined by the damper feed-
back potentiometer. The bypass controller is designed for use
on dampers with a range of rotation up to 90 degrees.
Damper
Position:
Display Units
% open
Default Value
0
Display Range
0 to 100
Forcible
No
Table 7 — Commissioning Maintenance
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
Bypass Commis (60 min)
Enable
Service
COMMISS
Damper Calibration
Disable
DMP_CAL
Zero Pressure Cal
Disable
ZR_PSCAL
Pressure Sensor Cal
Disable
PS_CAL
Damper Position
42
%OPEN
DMP_POS
System Pressure
0.00
in H2O
SP_SENSR
System Pressure Setpt
1.50
in H2O
SP_SETPT
Damper Cal Alarm
Normal
DAMP_CAL
Press Sensr Cal Alarm
Normal
SP_CAL
Summary of Contents for VVT 33ZC
Page 3: ...3 Fig 2 Bypass Controller Dimensions Fig 1 Bypass Controller Details...
Page 7: ...7 Fig 7 High Torque Actuator Wiring...
Page 8: ...8 Fig 8 High Torque Actuator with Linked Dampers Wiring...
Page 9: ...9 Fig 9 Field Supplied Linked Damper Wiring...
Page 10: ...10 Fig 10 Multiple Field Supplied Linked Damper Wiring...