background image

6

Install Field-Supplied Actuators —

Follow the damp-

er manufacturers recommended installation instructions with
the following recommendations.

Belimo Multi-Function technology actuators may be ordered

direct from Belimo. The following accessory actuators may be
used instead of the integrated actuator:
• NM24-MFT US P-30002 — 70 in.-lb actuators with

floating point control and 0 to 10 vdc feedback.

• AM24-MFT US P-30002 — 160 in.-lb actuators with

floating point control and 0 to 10 vdc feedback.
The following actuators may be used as linked actuators.

Up to four actuators may be linked to the main actuator:
• LM24-MFT US P-10002 — 35 in.-lb actuators with 0 to

10 vdc control and 0 to 10 vdc feedback.

• NM24-MFT US P-10002 — 70 in.-lb actuators with 0 to

10 vdc control and 0 to 10 vdc feedback.

• AM24-MFT US P-10002 — 160 in.-lb actuators with 0

to 10 vdc control and 0 to 10 vdc feedback.

FLOATING POINT HIGH-TORQUE ACTUATORS —
The field-supplied floating point high-torque actuators are
multi-function technology actuators intended for applications
where higher torque is needed for bypass operation. These
actuators would replace the integrated actuator on the bypass
controller. The actuators have three wires for power and
control and one 0-10VDC feedback wire to send a signal to the
bypass controller and any linked actuators. The three control
wires are 1(BLK), 2(RED), and 3(WHT). The 1(BLK) and
2 (RED) wires provide power to the actuator. These should be
wired to the same power source as the bypass controller
making sure wire 2 (RED) connects to J1-1 on the power plug
of the Bypass controller and wire 1 (BLK) connects to J5-2 the
common of the Bypass Controller power. See Fig. 7 and 8 for
wiring.

Polarity of the actuator and bypass controller power must be

the same for proper operation and to prevent damage to the
devices. A 1N4004 or 1N4007 diode must be placed across the
CCW and CW terminals of the bypass controller. The end of
the diode with the silver band tip (positive end) should be
placed in the CCW terminal along with Wire 3(WHT). The
other end of the diode should be placed in the CW terminal
with the actuator switch in the CW or default position. This
will make the damper rotate CCW when the CCW terminal is
energized and CW when the CW terminal is energized. For
reverse rotation the actuator switch may be changed to the
CCW position.

LINKED ACTUATORS — Field-supplied linked actuators
may be used to link to the bypass controller actuator. Install the
actuators per the manufacturer’s directions. Provide power for
the linked actuators by wiring 24 vac to the 1(BLK) and 2
(RED) wires. Maintain polarity if more than one actuator is
powered by the same power supply. Make sure the direction
rotation switches on the linked actuators are set to CW. Wire
the wire 3 (WHT) of the linked actuator(s) to the wire 5 (GRN)
of the controlling actuator. The linked actuator will then track
to the same damper position as the controlling actuator. See
Fig. 8-10 for wiring.

Linked actuators may be used to control off the integrated

actuator of the bypass controller actuator. Install the actuators
per the manufacturer’s directions. Provide power for the linked
actuators by wiring 24 vac to the 1 (BLK) and 2 (RED) wires.
Maintain polarity if more than one actuator is powered by the
same power supply. Make sure the direction rotation switches
on the linked actuators are set to CW. Connect wire 3 (WHT)
of the linked actuator to J4-7(DMPPOS).

Damper Stops —

For clockwise closed installations the

damper stop on the right side of the damper shaft is left at the
full clockwise position. The stop on the left side of the shaft
must be moved to stop the actuator at the full open position for
the damper. For example the Carrier round dampers rotate
45 degrees. Slide the left stop up to the 45 degree mark. Press
the actuator release button and rotate the damper CCW all the
way to the stop. The damper blade indicator should indicate
the damper is full open. Wire 5 (white) should be wired to
J4-7(DMPPOS). See Fig. 2.
NOTE: The rotation switch should be in the CW position for
correct feedback for this application. Reverse the rotation by
configuring the bypass controller for clockwise open and do
not change the switch from the CW position.

Connect the Carrier Network Communica-
tion Bus —

The bypass controllers connect to the bus in a

daisy chain arrangement. The bypass controller may be in-
stalled on a primary bus or on a secondary bus from the prima-
ry bus. Connecting to a secondary bus is recommended.

At any baud (9600, 19200, 38400 baud), the number of con-

trollers is limited to 239 zones maximum. Bus length may not
exceed 4000 ft, with no more than 60 total devices on any
1000-ft section. Optically isolated RS-485 repeaters are re-
quired every 1000 ft.

Summary of Contents for VVT 33ZC

Page 1: ...oordinate up to 31 additional zone controllers The purpose of the Linkage Coordinator zone relationship is to provide an efficient data path for communica tion between the zone controllers bypass cont...

Page 2: ...ding the damper shaft through the actuator clamp assembly See Fig 2 for details Remove the controller wiring access cover Secure the controller by installing the screw provided through the grommet in...

Page 3: ...3 Fig 2 Bypass Controller Dimensions Fig 1 Bypass Controller Details...

Page 4: ...ENSOR 1 6 J5 3 1 G CCN 3 3 G 1 1 5 1 6 1 J4 1 2 NOT USED NOT USED NOT USED DAT NOT USED NOT USED NOT USED NOT USED DAT TO COMMUNICATION BUS TO FEEDBACK POTENTIOMETER LINE VOLTAGE EQUIPMENT GROUND TO D...

Page 5: ...p the grommet into the hole until it is secure Pull on the leads of the duct sensor until the sensor is snug against the grommet 3 Connect the sensor leads to the bypass controller s termi nal board a...

Page 6: ...reverse rotation the actuator switch may be changed to the CCW position LINKED ACTUATORS Field supplied linked actuators may be used to link to the bypass controller actuator Install the actuators pe...

Page 7: ...7 Fig 7 High Torque Actuator Wiring...

Page 8: ...8 Fig 8 High Torque Actuator with Linked Dampers Wiring...

Page 9: ...9 Fig 9 Field Supplied Linked Damper Wiring...

Page 10: ...10 Fig 10 Multiple Field Supplied Linked Damper Wiring...

Page 11: ...s cable a color code system for the entire network is recommended to simplify installation and checkout See Table 4 for the recommended color code Table 4 Color Code Recommendations 3 Connect the othe...

Page 12: ...ew bypass pressure set point 10 Read the airflow with a measuring device If the reading varies from the screen value force the value to the mea sured value Once the pressure sensor is forced the contr...

Page 13: ...iable displays whether the leaving air temperature exceeds the heating or cooling limit configured in the Bypass Controller Service Configuration Table If Yes is displayed the System Pressure Set Poin...

Page 14: ...zone controller to turn the system fan off If the communication fails the damper calibration process will be terminated and this decision will be Disabled When the fan is off the zone controller will...

Page 15: ...NT Duct Temperature This variable displays the duct tempera ture at the bypass damper through a 10K thermistor with a measurement range from 40 to 245 F in 0 1 F increments Duct Temperature Display Un...

Page 16: ...efault Value Close Max Damper Alarm Limit This decision is used to gener ate alarms during system heating and cooling modes When the bypass damper position is greater than this configured limit and th...

Page 17: ...ease to within the zero tolerance 1 0 0 1 vdc of the sensor The alarm is disabled if this decision is set to Disable Press Sensr Cal Alarm Default Value Enable Display Range Enable Disable Duct Temp C...

Page 18: ...is off When the fan is off the bypass controller will drive its damper to the fully closed position The bypass controller will read the value of the actuator s feedback potentiometer until the value...

Page 19: ...l terminate the calibration Once at the fully open damper position the bypass controller will read the output voltage of the pressure sensor If the voltage reads within the range of 1 0 vdc 0 1 volt i...

Page 20: ...b 11a 13a Copyright 2004 Carrier Corporation SEN Fig 12 Bypass Controller Operation Flow Chart LEGEND BP Bypass BP_SETPT System Pressure Setpoint DAT Duct Air Temperature DMP_POS Damper Position LAT L...

Reviews: