                    CARRIER CORPORATION ©2010 

                    A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-437-01 · 11/19/2010 

 

Summary of Contents for UC Open XP

Page 1: ...e en n X XP P I IO O I In ns st ta al ll la at ti io on n a an nd d S St ta ar rt t u up p G Gu ui id de e CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol...

Page 2: ......

Page 3: ...ount the UC Open XP IO 18 To wire for power 19 To set UC Open XP IO s address 19 Wiring inputs and outputs 20 Input wiring specifications 20 Inputs UC Open XP IO 20 Binary outputs 21 To wire inputs an...

Page 4: ...Table of Contents ii UC Open XP UC Open XP IO FCC Compliance 37 CE Compliance 37 BACnet Compliance 37...

Page 5: ...4 Vac 10 50 60 Hz 20 VA power consumption 26 VA with BACview attached 26 Vdc 25 V min 30 V max Single Class 2 source only 100 VA or less BACnet Port Port 2a BACnet MS TP 9600 bps 19 2 kbps 38 4 kbps o...

Page 6: ...minimum of 10 000 hours of data retention during power outages Protection Incoming power and network connections are protected by non replaceable internal solid state polyswitches that reset themselv...

Page 7: ...0 2 cm 1 2 in 1 3 cm 13 64 in 5 cm Panel depth 2 in 5 1 cm Weight 1 1lb 0 5 kg BACnet support Conforms to the Advanced Application Controller B AAC Standard Device Profile as defined in ANSI ASHRAE St...

Page 8: ...Introduction 4 UC Open XP UC Open XP IO...

Page 9: ...inary outputs configured as dry contact normally open and must be powered from a Class 2 power source Protection Incoming power and network connections are protected by non replaceable internal solid...

Page 10: ...dimensions A B 10 5 8 in 27 0 cm 3 in 7 6 cm Mounting dimensions C D E 10 3 16 in 25 9 cm 1 1 2 in 3 8 cm 13 64 in 5 cm Panel depth 1 1 2 in 8 cm Weight 73 lbs 33 kg Listed by UL 916 Canadian Std C22...

Page 11: ...XP UC Open XP IO 7 Safety considerations Disconnect electrical power to the UC Open XP before wiring it Failure to follow this warning could cause electrical shock personal injury or damage to the con...

Page 12: ...under Reports in Field Assistant after installing your control program UC Open XP Installation Guide 1 Prepare a wire list using the points list Refer to the Appendix page 29 2 Use the wire list and t...

Page 13: ...llation and Start up Guide 5 Check out and commission the equipment To mount the UC Open XP When you handle the UC Open XP Do not contaminate the printed circuit board with fingerprints moisture or an...

Page 14: ...es to the screw terminal connector 5 Apply primary power to the transformer 6 Measure the voltage at the UC Open XP s power screw terminal connector to verify that the voltage is within the operating...

Page 15: ...UC Open XP Wiring the UC Open XP to the MS TP network The UC Open XP communicates using BACnet on an MS TP network segment communications at 9600 bps 19 2 kbps 38 4 kbps or 76 8 kbps Wire the control...

Page 16: ...hout the network segment 4 Verify that the MSTP jumper is set to MSTP 5 Set DIP switches 1 and 2 to the appropriate baud rate See the MSTP baud diagram on the UC Open XP The default baud rate is 76 8...

Page 17: ...elded 100 500 feet Shielded RTD 100 feet 30 meters 22 AWG Shielded SPT sensors 500 feet 152 meters 18 AWG Unshielded Inputs UC Open XP The UC Open XP has 12 inputs that accept the signal types describ...

Page 18: ...twice the cable length Acceptable voltage drop in the wire from the controller to the controlled device Resistance Ohms of the chosen wire gauge Maximum current Amps the controlled device requires to...

Page 19: ...e at the sensor end Connect the shield wire to the GND terminal with the ground wire Use only UI 1 or UI 2 for pulse counter or timed local override For an internally powered 4 20 mA sensor wire the s...

Page 20: ...act 0 5 Vdc 0 10 Vdc 0 20 mA RTD Set each input s Universal Input Mode Select jumper to the type of signal the input will receive Aux Power Out port Internally powered 4 20 mA Set the Select jumper to...

Page 21: ...17 5 Connect the analog output wiring to the screw terminals on the UC Open XP and to the controlled device 6 Set the AO Mode Select jumper to the type of device you are wiring the output to 7 Turn o...

Page 22: ...re or any foreign material Do not touch components or leads Handle the board by its edges Isolate from high voltage or electrostatic discharge Ensure that you are properly grounded Wiring restrictions...

Page 23: ...are present For the UC Open XP to recognize an attached expander you must turn on the expander before you turn on the UC Open XP 1 Turn off the UC Open XP IO s power jumper 2 Connect the input wiring...

Page 24: ...AWG 100 feet Unshielded 100 500 feet Shielded Thermistor Dry contact Pulse counter TLO 500 feet 152 meters 22 AWG 100 feet Unshielded 100 500 feet Shielded Inputs UC Open XP IO The UC Open XP IO has...

Page 25: ...ual wire For 2 conductor wires this is twice the cable length Acceptable voltage drop in the wire from the expander to the controlled device Resistance Ohms of the chosen wire gauge Maximum current Am...

Page 26: ...jumper to indicate the type of input WARNING Do not apply 24 Vac to these universal inputs 5 Connect binary output wiring to the BO screw terminals on the UC Open XP IO and to the controlled device 6...

Page 27: ...t INFO button to cycle through zone and outdoor air temperatures setpoints and local override time MODE button to cycle through custom programmed modes FAN SPEED button to adjust fan speed Local acces...

Page 28: ...and pull off the outer jacket of the Rnet cable s Do not nick the inner insulation Strip about 25 inch 6 cm of the inner insulation from each wire Outer Jacket Inner insulation 25 in 6 cm 2 Wire each...

Page 29: ...s For BACview6 Handheld keypad display unit Local Access port Temporary user interface for driver parameter access Virtual BACview software running on a laptop Local Access port Temporary user interfa...

Page 30: ...s when the controller receives data from the network segment there is an Rx LED for Ports 1 and 2 Tx Lights when the controller transits data from the network segment there is an Rx LED for Ports 1 an...

Page 31: ...off then on Download memory to the UC Open XP Replace the UC Open XP Restore factory defaults CAUTION To erase volatile memory data and restore factory default configuration settings This erases all...

Page 32: ...10 000 hours of data retention during power outages CAUTION Power must be ON to the UC Open XP when replacing the battery or your date time and trend data will be lost 1 Remove the battery from the co...

Page 33: ...GND Point Cable Inputs G Input Type Jumper Position of Pins I O Sensor code Equipment Name Point Name 3 5 0 10 Upper UI 1 3 5 Pulse Other Middle 3 5 4 20 Lower 4 5 0 10 Upper UI 2 4 5 Pulse Other Mid...

Page 34: ...ype Jumper Position of Pins I O Sensor code Equipment Name Point Name 1 2 mA Left 2 pins AO 1 Volt Right 2 pins 3 mA Left 2 pins AO 2 Volt Right 2 pins 5 6 0 10 N A AO 3 7 8 0 10 N A AO 4 9 10 0 10 N...

Page 35: ...Jumper UI 9 1 2 Therm Dry Contact Jumper 3 4 0 5V No Jumper UI 10 3 4 Therm Dry Contact Jumper 5 6 0 5V No Jumper UI 11 5 6 Therm Dry Contact Jumper 7 8 0 5V No Jumper UI 12 7 8 Therm Dry Contact Jump...

Page 36: ...endix A UC Open XP and UC Open XP IO wire lists 32 UC Open XP UC Open XP IO 7 8 N O N A BO 4 9 10 N O N A BO 5 11 12 N O N A BO 6 13 14 N O N A BO 7 15 16 N O N A BO 8 NOTE All inputs can be pulse inp...

Page 37: ...5 17 Duct Static Pressure 4 20mA transmitter Lower UI 10 AI 16 17 Indoor Air Quality CO2 4 20mA transmitter Lower UI 11 AI 18 20 Outdoor Air Quality CO2 4 20mA transmitter Lower UI 12 AI 19 20 Buildin...

Page 38: ...n PRESS Dry Contact Middle BI 6 BI 11 12 Smoke Purge PURGE Dry Contact Middle BI 7 BI 13 14 Enthaply Switch Input Dry Contact Middle BI 8 UI 9 AI 1 2 Preheat Coil Temp 10K Thermistor Middle UI 10 UI 1...

Page 39: ...UI 7 AI 12 14 Return Air Temp 10K Thermistor Middle UI 8 AI 13 14 Space RH 4 20mA transmitter Lower UI 9 N A UI 10 AI 16 17 Indoor Air Quality CO2 4 20mA transmitter Lower UI 11 AI 18 20 Outdoor Air...

Page 40: ...ation PRESS Dry Contact Middle BI 6 BI 11 12 Smoke Purge PURGE Dry Contact Middle BI 7 BI 13 14 Enthaply Switch Input Dry Contact Middle BI 8 UI 9 AI 1 2 Preheat Coil Temp 10K Thermistor Middle UI 10...

Page 41: ...cause harmful interference in which case the user will be required to correct the interference at his own expense CAUTION Changes or modifications not expressly approved by the responsible party for c...

Page 42: ......

Page 43: ......

Page 44: ...CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 437 01 11 19 2010...