UC Open XP installation
8
UC Open XP/UC Open XP IO
To install the UC Open XP:
1
Mount the controller.
(page 9)
2
Wire the controller for power.
(page 10)
3
Set the controller's address.
(page 10)
4
Wire expanders to the controller.
(page 18)
5
Wire inputs and outputs
(page 13).
6
Wire sensors to the controller.
(page 23)
To install the UC Open XP into an i-Vu Open Control System
You must complete the following procedures to successfully install your UC Open XP into an i-Vu Open Control
System. Use the Help in the referenced software for detailed descriptions of these procedures.
ApplicationBuilder or Snap
1
Use ApplicationBuilder or Snap to create control program(s) for your UC Open XP.
2
If applicable, print the Sequence of Operation created by ApplicationBuilder, which includes the points
list.
NOTE
You can create a points list under
Reports
in Field Assistant after installing your control program.
UC Open XP Installation Guide
1
Prepare a wire list using the points list. Refer to the
Appendix
(page 29).
2
Use the wire list and the following installation procedures to install and wire I/O points to your UC Open
XP and expander, if applicable.
i-Vu/Field Assistant
1
Complete the
Discovery
process to upload the controller to the database.
2
In
Discovery
>
Setup
, select
Add Control Program
, upload control program and graphic to i-Vu/FA, then
download to the controller.
3
Select the controller in the navigation tree and go to
Properties
page >
I/O Points
tab to assign channel
numbers to the physical points.
NOTE
39m AHU Equipment has pre-assigned IO channels. See
Appendix B
(page 33). You must assign
IO channels in all other applications by:
○
Entering your channel numbers under
Num
, using your wire list
○
Entering your expander address under
Exp
, if applicable
○
Selecting the appropriate value under
Sensor/Actuator Type
, if applicable
UC Open XP installation
Summary of Contents for UC Open XP
Page 2: ......
Page 8: ...Introduction 4 UC Open XP UC Open XP IO...
Page 42: ......
Page 43: ......