UC Open XP/UC Open XP IO
5
UC Open XP IO specifications
Power
24 Vac ±10%, 50–60 Hz
13 VA power consumption
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
Binary inputs
IN 1 - 8 are binary only and support pulse counting up to 10 Hertz,
dry contact only.
Universal inputs
IN 9 - 16 are universal inputs, jumper selectable between
thermistor/dry contact and 0-5 Vdc.
Input resolution
10 bit A/D
Input pulse frequency
10 pulses per second max. Minimum pulse width (on or off time)
required for each pulse is 50 msec.
Binary outputs
8 binary outputs, configured as dry contact, normally open, and
must be powered from a Class 2 power source.
Protection
Incoming power and network connections are protected by non-
replaceable internal solid-state polyswitches that reset themselves
when the condition that causes a fault returns to normal. The
power, network, input, and output connections are also protected
against voltage transient and surge events.
Status indicators
LED's indicate status of communications, running, errors, and
outputs
Environmental operating
range
0 to 140° F (-18 to 60°C), 0 to 90% relative humidity, non-
condensing
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-
condensing
Physical
Rugged aluminum housing with removable screw terminals
Summary of Contents for UC Open XP