2
UC Open XP/UC Open XP IO
Input pulse frequency
10 pulses per second. Minimum pulse width (on or off time)
required for each pulse is 50 msec.
Input resolution
12 bit A/D
Binary outputs
6 binary outputs, configured as dry contact, normally open or
normally closed, must be powered from a Class 2 power source.
Analog outputs
6 analog outputs:
•
1 and 2 are configurable for 0-10V or 0-20mA
•
3 - 6 are 0-10V only
Output resolution
8 bit D/A
Real time clock
Battery-backed real time clock keeps track of time in the event of a
power failure
Battery
10-year Lithium CR2032 battery provides a minimum of 10,000
hours of data retention during power outages
Protection
Incoming power and network connections are protected by non-
replaceable internal solid-state polyswitches that reset themselves
when the condition that causes a fault returns to normal. The
power, network, input, and output connections are also protected
against voltage transient and surge events.
Status indicators
LED's indicate status of communications, running, errors, and
power. LED indicators for transmit/receive for Port 1 and Port 2a
and for each of the 12 outputs.
Environmental operating
range
0 to 140° F (-18 to 60°C), 0 to 90% relative humidity, non-
condensing
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-
condensing
Physical
Rugged aluminum housing with removable screw terminals