7.5.2 - Variator sub-code alarms

No.

Alarm/alert 
level

Description

Action taken

Variator sub-code alarms

2

Alarm

Error at function "Live Zero"

Contact Carrier Service

4

Alarm

Phase loss detection

Check the VFD supply voltage and the phase balance (±3%)

7

Alarm

Overvoltage detected

Contact Carrier Service

8

Alarm

Undervoltage detected

Contact Carrier Service

9

Alarm

Inverter overload

Check the VFD output current/compressor current

10

Alarm

Motor overheated

Check the motor temperature

11

Alarm

Motor overheat thermistor defective

Contact Carrier Service

12

Critical alarm

Torque limit exceeded

Check the VFD output current/compressor current

13

Critical alarm

Overcurrent detected

Check the VFD output current/compressor current

14

Critical alarm

Poor earthing

Check if an earth fault exists

16

Critical alarm

Motor short-circuit detected

Check if there is a short-circuit at the VFD terminals

17

Alarm

Communication loss with the frequency converter

Check the connections and the shielding of the serial communication cable

23**

Alarm

Internal fan operating problem

Check the internal fan rotation

25

Alarm

Brake resistor short-circuited

Contact Carrier Service

26

Alarm

Capacity dissipated by the brake resistor too high

Contact Carrier Service

28

Alarm

Brake verification

Contact Carrier Service

29

Critical alarm

VFD temperature too high

Space temperature too high or VFD ventilation obstructed or damaged

30

Critical alarm

Motor phase U missing

Check wiring of phase U

31

Critical alarm

Motor phase V missing

Check wiring of phase V

32

Critical alarm

Motor phase W missing

Check wiring of phase W

33

Alarm

Current demand too high

Let the VFD cool down for 20 minutes before starting it

34

Alarm

Problem on the site communication bus

Check the connections and the shielding of the serial communication cable

36

Alarm

Supply voltage problem

Check the VFD supply voltage and the phase balance (±3%)

38

Critical alarm

Internal frequency variator problem

Contact Carrier Service

47

Alarm

24 V supply too low

Contact Carrier Service

48

Alarm

1.8 V supply too low

Contact Carrier Service

57*** Alarm

No response from AMA

Contact Carrier Service

65

Alarm

Control board overheated

Check the space temperature and the VFD fan

67

Critical alarm

Option configuration modifications

Contact Carrier Service

68

Alarm

Numerical input 37 - emergency stop activated

Contact Carrier Service

71

Alarm

Emergency stop at thermistor PTC1

Contact Carrier Service

72

Critical alarm

Emergency stop

Contact Carrier Service

80

Alarm

Frequency variator reset to default values

Contact Carrier Service

94

Alarm

Curve end

Contact Carrier Service

95

Alarm

Torque loss

Contact Carrier Service

243

Alarm

IGBT defective

Contact Carrier Service

251† Critical alarm

New parts detached

Contact Carrier Service

301

Alarm

Problem in set 1 of the configuration parameters

Check the communication bus connections and the software version

302

Alarm

Problem in set 2 of the configuration parameters

Check the communication bus connections and the software version

303

Alarm

Problem in set 3 of the configuration parameters

Check the communication bus connections and the software version

Variator sub-code alerts

 (WY-XXX*)

1

Alert

10 V supply to low

Contact Carrier Service

2

Alert

Error at function "Live Zero"

Contact Carrier Service

3

Alert

No motor

Check the motor connections

4

Alert

Phase loss detection

Check the VFD supply voltage and the phase balance (±3%)

5

Alert

Intermediate voltage too high

Check the VFD supply voltage and the phase balance (±3%)

6

Alert

Intermediate voltage too high

Check the VFD supply voltage and the phase balance (±3%)

7

Alert

Intermediate voltage too high

Contact Carrier Service

8

Alert

Intermediate voltage too high

Contact Carrier Service

9

Alert

Inverter overload

Check the VFD output current/compressor current

10

Alert

Motor overheated

Check the motor temperature

11

Alert

Motor overheat thermistor defective

Contact Carrier Service

12

Alert

Torque limit exceeded

Check the VFD output current/compressor current

13

Alert

Overcurrent detected

Check the VFD output current/compressor current

14

Alert

Poor earthing

Check if an earth fault exists

17

Alert

Motor short-circuit detected

Check the connections and the shielding of the serial communication cable

23**

Alert

Communication loss with the frequency converter

Check the internal fan rotation

25

Alert

Brake resistor short-circuited

Contact Carrier Service

26

Alert

Capacity dissipated by the brake resistor too high

Contact Carrier Service

28

Alert

Brake verification

Contact Carrier Service

34

Alert

Problem on the site communication bus

Check the connections and the shielding of the serial communication cable

36

Alert

Supply voltage problem

Check the VFD supply voltage and the phase balance (±3%)

47

Alert

24 V supply too low

Contact Carrier Service

49

Alert

Motor speed limit exceeded

Contact Carrier Service

59

Alert

Current limit exceeded

Check the VFD output current/compressor current

62

Alert

Frequency at the maximum limit

Check the VFD output current/compressor current

64

Alert

Voltage limit

Supply voltage too low

65

Alert

Control board overheated

Check the space temperature and the VFD fan

66

Alert

Internal frequency variator temperature too low

Space temperature too low

Y = 0: circuit A; Y=1: circuit B; XXX = sub-code

** 

Error 24 and 104 possible

***  Error 50 to 58 possible
† 

Error 250 or 70 possible

††  Not applicable for variator size 102

Summary of Contents for Touch Pilot 30XW-V

Page 1: ...CONTROLS MANUAL Touch Pilot Control 30XW V 30XWHV 30XW V ZE Original document AquaForce PUREtec with R 1234ze E...

Page 2: ...tch 17 5 6 Heating cooling selection 17 5 7 Control point 17 5 8 Capacity limitation 18 5 9 Night mode 18 5 10 Capacity control 18 5 11 Compressor short cycling protection 18 5 12 Option 152 saturated...

Page 3: ...2 1 General Touch Pilot is a system for controlling 30XW V 30XWHV single circuit or dual circuit water cooled units with R 134a refrigerant as well as 30XW V ZE single circuit or dual circuit water c...

Page 4: ...lure The green LED flashes continuously on all boards to show that the board is communicating correctly over its internal bus If the LED is not flashing this indicates a LEN bus wiring problem When th...

Page 5: ...flow setpoint of the water flow switch 3 6 Frequency variator The frequency variator is used to control the compressor It allows compressor start up and capacity control by modify ing the supply freq...

Page 6: ...s allows control of the unit occupancy occupied unoccupied Contact 3bis capacity limit selection 2 J4 Ch09 73A 74A NRCP2 BASE EMM A3 energy management This contact is only available with the energy ma...

Page 7: ...l features 4 3 1 Buttons Unit is running or in standby Unit is off Home Access to menus Not logged in Logged in No alarm Alert Alarm Back Previous page Next page More information Click this button Val...

Page 8: ...rce level is lower than the equipment controller s level 4 4 On off screen 4 4 1 Unit start up With the unit in Local Off mode press to display the list of operating modes Select the required mode Sho...

Page 9: ...n a forceable point of a data screen 4 10 Time schedule screen Forced Auto Forced value The auto button cancels a forced point 1 Selection of the applicable days for the time schedule 2 Modification o...

Page 10: ...7 0 to 2 Heat cool select Heating cooling selection via CCN or BACnet IP option 8 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 9 0 to 2 Setpoint select Setpoint selection via CCN or BACnet IP option 10...

Page 11: ...te On Off Switch Remote On Off Switch 2 open closed Remote HeatCool Switch Heating cooling selection switch 3 open closed Remote Setpoint Switch Setpoint selection switch 4 open closed Limit Switch 1...

Page 12: ...tion Evaporator pump rotation 6 yes no Pump Periodic Start Periodic pump start up 7 yes no Night Low Noise Active Night mode active 8 yes no Master Slave Active Master slave active 9 yes no Auto Chang...

Page 13: ...trol 11 00 00 0 Night Mode Start Hour Night mode start hour 12 00 00 0 Night Mode End Hour Night mode end hour 13 100 Night capacity Limit Night mode capacity limit 14 yes no no Current Limit select A...

Page 14: ...Full Reset Value Outdoor temperature max reset 21 0 to 13 9 0 C Delta T No Reset Value Delta T no reset 22 0 to 13 9 0 C Delta T Full Reset Value Delta T max reset 23 0 to 20 0 mA Current No Reset Val...

Page 15: ...Alarm 5 Current JBus alarm 5 4 13 3 BROCASTS menu Broadcast menu Name Format Value Description Ccnbroad 0 1 2 2 Activates broadcast 0 deactivated 1 broadcast time holidays on the network 2 broadcast t...

Page 16: ...start up is 1 minute configurable between 1 and 15 minutes the pump will run for at least one minute before the first compressor starts The pump is kept running for 20 seconds after the unit goes to...

Page 17: ...ling selection For units configured in the heat pump mode heating cooling selection can be controlled in various ways depending on the active operating type locally at the unit using the HC_SEL item i...

Page 18: ...ading functions can also affect the temperature control accuracy Compressors are started in a sequence designed to equalise the number of start ups value weighted by their operating time 5 11 Compress...

Page 19: ...y period 12 HOLDY_13 Holiday period 13 HOLDY_14 Holiday period 14 HOLDY_15 Holiday period 15 HOLDY_16 Holiday period 16 5 14 Option 156 energy management option This option requires the installation o...

Page 20: ...building management system or the programmable controllers to communicate with the Touch Pilot interface It is activated if the optional BACnet activation key dongle is present on the electronic contr...

Page 21: ...circuit has been shut down due to a fault The Reset alarms menu on the main interface displays up to five fault codes that are active on the unit 7 3 Resetting alarms When the cause of the alarm has...

Page 22: ...rd 1 Automatic if the communi cation is re established Unit shuts down Bus installation fault or defective slave board 23 4501 Communication loss with auxiliary board 1 As above Unit continues to oper...

Page 23: ...r pump connection 63 10074 Fault condenser pump 2 Manual Unit shuts down Pump overheats or poor pump connection 64 10078 High discharge gas temperature circuit A Manual Circuit A shuts down Defective...

Page 24: ...ontact Carrier Service 95 Alarm Torque loss Contact Carrier Service 243 Alarm IGBT defective Contact Carrier Service 251 Critical alarm New parts detached Contact Carrier Service 301 Alarm Problem in...

Page 25: ...ert Curve end Contact Carrier Service 95 Alert Torque loss Contact Carrier Service 96 Alert Start up delayed Contact Carrier Service 97 Alert Stop delayed Contact Carrier Service 98 Alert Clock proble...

Page 26: ......

Page 27: ......

Page 28: ...om www certiflash com Order No 13475 12 2016 Supersedes order No 13475 07 2016 Manufactured for CARRIER in France The manufacturer reserves the right to change the specification without prior notice P...

Reviews: