Associated table: RESETCFG - Reset Confi guration (Setpoint reset)
No.
Status
Default
Unit
Displayed text*
Description
1
0 to 4
0
-
Cooling Reset Select
Cooling reset selection
2
0 to 4
0
-
Heating Reset Select
Heating reset selection
3
0 = None, 1 = OAT
0 = none, 1 = outdoor temperature
4
2 = Delta T, 4 = Space Temp
2 = delta T, 4 = space temperature
5
3 = 4-20 mA control
3 = 4-20 mA control
6
7
Cooling
Cooling mode
8
-10.0 to 51.7
-10
°C
OAT No Reset Value
Outdoor temperature, no reset
9
-10.0 to 51.7
-10
°C
OAT Full Reset Value
Outdoor temperature, max. reset
10
0 to 13.9
0
^C
Delta T No Reset Value
Delta T, no reset
11
0 to 13.9
0
^C
Delta T Full Reset Value
Delta T, max. reset
12
0 to 20
0
mA
Current No Reset Value
Current, no reset
13
0 to 20
0
mA
Current Full Reset Value
Current, max. reset
14
-10.0 to 51.7
-10
°C
Space T No Reset Value
Space temperature, no reset
15
-10.0 to 51.7
-10
°C
Space T Full Reset Value
Space temperature, max. reset
16
-30 to 30
0
^C
Cooling Reset Deg. Value
Maximum cooling reset value
17
18
Heating
Heating mode
19
-10.0 to 51.7
-10
°C
OAT No Reset Value
Outdoor temperature, no reset
20
-10.0 to 51.7
-10
°C
OAT Full Reset Value
Outdoor temperature, max. reset
21
0 to 13.9
0
^C
Delta T No Reset Value
Delta T, no reset
22
0 to 13.9
0
^C
Delta T Full Reset Value
Delta T, max. reset
23
0 to 20
0
mA
Current No Reset Value
Current, no reset
24
0 to 20
0
mA
Current Full Reset Value
Current, max. reset
25
-10.0 to 51.7
-10
°C
Space T No Reset Value
Space temperature, no reset
26
-10.0 to 51.7
-10
°C
Space T Full Reset Value
Space temperature, max. reset
27
-16.7 to 16.7
0
^C
Heating Reset Deg. Value
Maximum heating reset value
Associated table: DATETIME - Date/time confi guration
Name
Format
Units
Description
d_of_m
1 to 31
-
Day of the month
month
1 to 12
-
Month
year
0 to 99
-
Year
dow
1 to 7
-
Day of the week
hour
0 to 24
h
Hour
minutes
0 to 59
min
Minutes
dlig_off
yes/no
-
Winter time change-over active?
tod_hol
yes/no
-
Holiday today?
tom_hol
yes/no
-
Holiday tomorrow?
Associated table: CTRL_ID - Control identifi cation
Name
Format
Description
elemt_nb
1 to 239
Element number
bus_nb
0 to 239
Bus number
baudrate
9600 to 38400
Communication speed
30XWV Touch Pilot
Device description
---------------------
Location description
CSA-SR-20M49010
Software number
---------------------
Serial number
*
Depends on selected language, default is English
Associated table: USERCONF - User confi guration
No.
Status
Default
Unit
Displayed text*
Description
1
1 to 9999
11
-
User Password
User password