5.7.2 - Reset

Reset  means  the  active  setpoint  is  modified  so  that  less 

machine capacity is required (in cooling mode the setpoint 

is increased, in heating mode it is decreased). This modification 

is in general a reaction to a drop in the load. For the Touch 

Pilot control system, the reset source can be configured in 

the menu Status => RESETCFG: it can be based on the 
outdoor temperature (gives a measure of the load trends for 
the building) or used with the energy management option at 
the reset setpoint. In response to a drop in the space 
temperature or to a drop in 

T, the cooling setpoint is 

normally reset upwards to optimise unit performance.

In the three cases the reset parameters, i.e. slope, source and 

maximum value, are configurable in the Setpoint menu. Reset 

is a linear function based on three parameters:
• 

A reference at which reset is zero (space temperature or 

T - no reset value).

• 

A reference at which reset is maximum (space tempera-
ture or 

T - full reset value).

• 

The maximum reset value. 

Reset example in cooling mode for the space 

temperature

Legend

Maximum reset value

Space temperature for zero reset

Space temperature for maximum reset

Building load

Space temperature (SPACETEMP)

R

eset v

alue

% Building load

5.9 - Night mode

The  night  period  is  defined  (see  menu  Config  =>  GEN_

CONF) by a start time and an end time that are the same for 
each day of the week. During the night period unit capacity 
is limited

 (a maximum capacity value can be configured - see 

configuration menu GEN_CONF).

5.10 - Capacity control

This function adjusts the compressor capacity to keep the 
heat exchanger water temperature at its setpoint. The control 
system continuously takes account of the temperature error 
with respect to the setpoint, as well as the rate of change in 
this error and the difference between entering and leaving 
water temperatures, in order to determine the optimum 
moment at which to add or withdraw capacity.

In addition, the high pressure or low pressure unloading 
functions can also affect the temperature control accuracy. 
Compressors are started in a sequence designed to equalise the 
number of start-ups (value weighted by their operating time).

5.11 - Compressor short cycling protection

The Touch Pilot control constantly monitors the control point 
which determines the operation of compressor(s). Compressors 
are turned on and off in order to maintain the required 
control point and satisfy the current cooling/heating demand. 

To avoid the risk of compressor short cycling, the Touch Pilot 
control provides a protection that prevents the premature 

starting of compressors. The service-configured temperature 

threshold (acting upon the control point) is used for 
compressor(s) control. 

This compressor short cycling protection can be enabled via 
the touch screen by setting the “short cycle management” 
parameter in the General Configuration menu (GEN_
CONF) to “yes”.

5.12 - Option 152 - saturated condensing temperature 

control

Saturated condensing temperature control is assured if the 
three-way valve option is selected. The saturated condensing 

temperature is controlled based on a fixed setpoint that can 
be  configured  by  the  user  via  the  SETPOINT  table. The 
three-way  valve  control  can  be  configured  by  the  service 

department via the SERVICE table.

5.8 - Capacity limitation

The Touch Pilot control system allows limitation of the unit 
capacity, using one of two methods:
• 

by means of user-controlled volt-free contacts. The units 
without energy management option only have one 
contact (control contact 3). The units equipped with 
energy management option permit three capacity 
limitation levels (2 contacts). The unit capacity can never 
exceed the limit setpoint activated by these contacts. The 

limit setpoints can be modified in the Setpoint table.

• 

by means of a capacity limitation setpoint output on the 
energy management board. The capacity limitation 
value in night mode is selectable if the value is below 
the selected limit. A limit value of 100% means that the 
unit can use all capacity stages.

ATTENTION: In certain conditions, the unit power con-
sumption can exceed the capacity limitation threshold to 
protect the compressors. 

Summary of Contents for Touch Pilot 30XW-V

Page 1: ...CONTROLS MANUAL Touch Pilot Control 30XW V 30XWHV 30XW V ZE Original document AquaForce PUREtec with R 1234ze E...

Page 2: ...tch 17 5 6 Heating cooling selection 17 5 7 Control point 17 5 8 Capacity limitation 18 5 9 Night mode 18 5 10 Capacity control 18 5 11 Compressor short cycling protection 18 5 12 Option 152 saturated...

Page 3: ...2 1 General Touch Pilot is a system for controlling 30XW V 30XWHV single circuit or dual circuit water cooled units with R 134a refrigerant as well as 30XW V ZE single circuit or dual circuit water c...

Page 4: ...lure The green LED flashes continuously on all boards to show that the board is communicating correctly over its internal bus If the LED is not flashing this indicates a LEN bus wiring problem When th...

Page 5: ...flow setpoint of the water flow switch 3 6 Frequency variator The frequency variator is used to control the compressor It allows compressor start up and capacity control by modify ing the supply freq...

Page 6: ...s allows control of the unit occupancy occupied unoccupied Contact 3bis capacity limit selection 2 J4 Ch09 73A 74A NRCP2 BASE EMM A3 energy management This contact is only available with the energy ma...

Page 7: ...l features 4 3 1 Buttons Unit is running or in standby Unit is off Home Access to menus Not logged in Logged in No alarm Alert Alarm Back Previous page Next page More information Click this button Val...

Page 8: ...rce level is lower than the equipment controller s level 4 4 On off screen 4 4 1 Unit start up With the unit in Local Off mode press to display the list of operating modes Select the required mode Sho...

Page 9: ...n a forceable point of a data screen 4 10 Time schedule screen Forced Auto Forced value The auto button cancels a forced point 1 Selection of the applicable days for the time schedule 2 Modification o...

Page 10: ...7 0 to 2 Heat cool select Heating cooling selection via CCN or BACnet IP option 8 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 9 0 to 2 Setpoint select Setpoint selection via CCN or BACnet IP option 10...

Page 11: ...te On Off Switch Remote On Off Switch 2 open closed Remote HeatCool Switch Heating cooling selection switch 3 open closed Remote Setpoint Switch Setpoint selection switch 4 open closed Limit Switch 1...

Page 12: ...tion Evaporator pump rotation 6 yes no Pump Periodic Start Periodic pump start up 7 yes no Night Low Noise Active Night mode active 8 yes no Master Slave Active Master slave active 9 yes no Auto Chang...

Page 13: ...trol 11 00 00 0 Night Mode Start Hour Night mode start hour 12 00 00 0 Night Mode End Hour Night mode end hour 13 100 Night capacity Limit Night mode capacity limit 14 yes no no Current Limit select A...

Page 14: ...Full Reset Value Outdoor temperature max reset 21 0 to 13 9 0 C Delta T No Reset Value Delta T no reset 22 0 to 13 9 0 C Delta T Full Reset Value Delta T max reset 23 0 to 20 0 mA Current No Reset Val...

Page 15: ...Alarm 5 Current JBus alarm 5 4 13 3 BROCASTS menu Broadcast menu Name Format Value Description Ccnbroad 0 1 2 2 Activates broadcast 0 deactivated 1 broadcast time holidays on the network 2 broadcast t...

Page 16: ...start up is 1 minute configurable between 1 and 15 minutes the pump will run for at least one minute before the first compressor starts The pump is kept running for 20 seconds after the unit goes to...

Page 17: ...ling selection For units configured in the heat pump mode heating cooling selection can be controlled in various ways depending on the active operating type locally at the unit using the HC_SEL item i...

Page 18: ...ading functions can also affect the temperature control accuracy Compressors are started in a sequence designed to equalise the number of start ups value weighted by their operating time 5 11 Compress...

Page 19: ...y period 12 HOLDY_13 Holiday period 13 HOLDY_14 Holiday period 14 HOLDY_15 Holiday period 15 HOLDY_16 Holiday period 16 5 14 Option 156 energy management option This option requires the installation o...

Page 20: ...building management system or the programmable controllers to communicate with the Touch Pilot interface It is activated if the optional BACnet activation key dongle is present on the electronic contr...

Page 21: ...circuit has been shut down due to a fault The Reset alarms menu on the main interface displays up to five fault codes that are active on the unit 7 3 Resetting alarms When the cause of the alarm has...

Page 22: ...rd 1 Automatic if the communi cation is re established Unit shuts down Bus installation fault or defective slave board 23 4501 Communication loss with auxiliary board 1 As above Unit continues to oper...

Page 23: ...r pump connection 63 10074 Fault condenser pump 2 Manual Unit shuts down Pump overheats or poor pump connection 64 10078 High discharge gas temperature circuit A Manual Circuit A shuts down Defective...

Page 24: ...ontact Carrier Service 95 Alarm Torque loss Contact Carrier Service 243 Alarm IGBT defective Contact Carrier Service 251 Critical alarm New parts detached Contact Carrier Service 301 Alarm Problem in...

Page 25: ...ert Curve end Contact Carrier Service 95 Alert Torque loss Contact Carrier Service 96 Alert Start up delayed Contact Carrier Service 97 Alert Stop delayed Contact Carrier Service 98 Alert Clock proble...

Page 26: ......

Page 27: ......

Page 28: ...om www certiflash com Order No 13475 12 2016 Supersedes order No 13475 07 2016 Manufactured for CARRIER in France The manufacturer reserves the right to change the specification without prior notice P...

Reviews: