background image

17

5.5 - Water flow switch

The controller is configurable. The configuration depends on 

the unit size and is made automatically at the start-up. 

If the measured flow rate in the water loop is lower than the 
configured flow rate, an alarm condition shuts off the unit.

5.7.1 - Active setpoint

Two setpoints can be selected. Usually, the second cooling 
setpoint is used for unoccupied periods. Depending on the 
current operation type, the active setpoint can be selected 
by choosing the item in the table Status => Genunit, with the 
volt-free user contacts, with network commands or with the 
setpoint timer program (schedule 2).

The following tables summarise the possible selections 
depending on the control types (local, remote or network) 
and the following parameters:

• 

Setpoint select in local control

: item “Setpoint select” 

in the table Status => Genunit permits selection of the 
active setpoint, if the unit is in local operating type.

• 

Control contacts 2: 

status of control contact 2.

• 

Schedule 2 status:

 schedule for setpoint selection.

5.7 - Control point

The control point represents the water temperature that the 
unit must satisfy.

In cooling mode the evaporator outlet water is controlled by 
default, but the evaporator inlet water can also be controlled 

(requires a Service configuration modification).

In heating mode the condenser outlet water is controlled by 
default, but the condenser inlet water can also be controlled 

(requires a Service configuration modification).

Control point = active se reset

Parameter status

On/off status

Control type

Heating/cooling selection 

in local mode

Heating/cooling contact 

in remote mode

HC_SEL

Operating mode

Off

-

-

-

-

Cooling

On

Local

Cooling

-

-

Cooling

On

Local

Heating

-

-

Heating 

On

Remote

-

On cooling

-

Cooling

On

Remote

-

On heating

-

Heating

On

Network

-

-

Cooling

Cooling

On

Network

-

-

Heating

Heating

5.6 - Heating/cooling selection

For units configured in the heat pump mode, heating/cooling 

selection can be controlled in various ways, depending on 
the active operating type:
• 

locally at the unit using the HC_SEL item in the 
GENUNIT table,

• 

remotely via the heating/cooling selection contact, if 
the unit is in the Remote mode operating type,

• 

via a CCN or BACnet/IP (option) network command, 
if the unit is in the network operating type. 

LOCAL OPERATING MODE

Parameter status 

Active setpoint

Heating/cooling operating mode Local setpoint selection Ice storage configuration* Ice storage contact status*  

Schedule 2 status

Cooling

csp 1

-

-

-

Cooling setpoint 1

Cooling

csp 2

-

-

-

Cooling setpoint 2

Cooling

auto

Activated

Open

Unoccupied

Ice storage setpoint 

Cooling

auto

Activated

Closed

Unoccupied

Cooling setpoint 2

Cooling

auto

-

-

Occupied

Cooling setpoint 1

Cooling

auto

Deactivated

-

Unoccupied 

Heating setpoint 2

Heating

hsp 1

-

-

-

Heating setpoint 1

Heating

hsp 2

-

-

-

Heating setpoint 2

Heating

auto

-

-

Occupied

Heating setpoint 1

Heating

auto

-

-

Unoccupied

Heating setpoint 2

REMOTE OPERATING MODE

Parameter status

Active setpoint

Heating/cooling operating mode Local setpoint selection Ice storage configuration* Ice storage contact status*  

Control contact 2

Cooling

csp control 

-

-

-

Control setpoint

Cooling

-

-

-

csp 1 (open)

Cooling setpoint 1

Cooling

-

-

-

csp 2 (closed)

Cooling setpoint 2

Cooling

-

Activated

-

Open

Cooling setpoint 1

Cooling

-

Activated

Open

Closed 

Ice storage setpoint

Cooling

-

Activated

Closed

Closed 

Cooling setpoint 2

Heating

-

-

-

Open

Heating setpoint 1

Heating

-

-

-

Closed 

Heating setpoint 2

NETWORK OPERATING MODE

Parameter status

Active setpoint

Heating/cooling operating mode Local setpoint selection Ice storage configuration* Ice storage contact status* 

Schedule 2 status

Cooling

-

-

-

Occupied

Cooling setpoint 1

Cooling

-

-

-

Unoccupied

Cooling setpoint 2

Cooling

-

Activated

Open

Unoccupied

Ice storage setpoint

Cooling

-

Activated

Closed

Unoccupied 

Cooling setpoint 2

Heating

-

-

-

Occupied

Heating setpoint 1

Heating

-

-

-

Unoccupied

Heating setpoint 2

* Only with energy management option

Summary of Contents for Touch Pilot 30XW-V

Page 1: ...CONTROLS MANUAL Touch Pilot Control 30XW V 30XWHV 30XW V ZE Original document AquaForce PUREtec with R 1234ze E...

Page 2: ...tch 17 5 6 Heating cooling selection 17 5 7 Control point 17 5 8 Capacity limitation 18 5 9 Night mode 18 5 10 Capacity control 18 5 11 Compressor short cycling protection 18 5 12 Option 152 saturated...

Page 3: ...2 1 General Touch Pilot is a system for controlling 30XW V 30XWHV single circuit or dual circuit water cooled units with R 134a refrigerant as well as 30XW V ZE single circuit or dual circuit water c...

Page 4: ...lure The green LED flashes continuously on all boards to show that the board is communicating correctly over its internal bus If the LED is not flashing this indicates a LEN bus wiring problem When th...

Page 5: ...flow setpoint of the water flow switch 3 6 Frequency variator The frequency variator is used to control the compressor It allows compressor start up and capacity control by modify ing the supply freq...

Page 6: ...s allows control of the unit occupancy occupied unoccupied Contact 3bis capacity limit selection 2 J4 Ch09 73A 74A NRCP2 BASE EMM A3 energy management This contact is only available with the energy ma...

Page 7: ...l features 4 3 1 Buttons Unit is running or in standby Unit is off Home Access to menus Not logged in Logged in No alarm Alert Alarm Back Previous page Next page More information Click this button Val...

Page 8: ...rce level is lower than the equipment controller s level 4 4 On off screen 4 4 1 Unit start up With the unit in Local Off mode press to display the list of operating modes Select the required mode Sho...

Page 9: ...n a forceable point of a data screen 4 10 Time schedule screen Forced Auto Forced value The auto button cancels a forced point 1 Selection of the applicable days for the time schedule 2 Modification o...

Page 10: ...7 0 to 2 Heat cool select Heating cooling selection via CCN or BACnet IP option 8 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 9 0 to 2 Setpoint select Setpoint selection via CCN or BACnet IP option 10...

Page 11: ...te On Off Switch Remote On Off Switch 2 open closed Remote HeatCool Switch Heating cooling selection switch 3 open closed Remote Setpoint Switch Setpoint selection switch 4 open closed Limit Switch 1...

Page 12: ...tion Evaporator pump rotation 6 yes no Pump Periodic Start Periodic pump start up 7 yes no Night Low Noise Active Night mode active 8 yes no Master Slave Active Master slave active 9 yes no Auto Chang...

Page 13: ...trol 11 00 00 0 Night Mode Start Hour Night mode start hour 12 00 00 0 Night Mode End Hour Night mode end hour 13 100 Night capacity Limit Night mode capacity limit 14 yes no no Current Limit select A...

Page 14: ...Full Reset Value Outdoor temperature max reset 21 0 to 13 9 0 C Delta T No Reset Value Delta T no reset 22 0 to 13 9 0 C Delta T Full Reset Value Delta T max reset 23 0 to 20 0 mA Current No Reset Val...

Page 15: ...Alarm 5 Current JBus alarm 5 4 13 3 BROCASTS menu Broadcast menu Name Format Value Description Ccnbroad 0 1 2 2 Activates broadcast 0 deactivated 1 broadcast time holidays on the network 2 broadcast t...

Page 16: ...start up is 1 minute configurable between 1 and 15 minutes the pump will run for at least one minute before the first compressor starts The pump is kept running for 20 seconds after the unit goes to...

Page 17: ...ling selection For units configured in the heat pump mode heating cooling selection can be controlled in various ways depending on the active operating type locally at the unit using the HC_SEL item i...

Page 18: ...ading functions can also affect the temperature control accuracy Compressors are started in a sequence designed to equalise the number of start ups value weighted by their operating time 5 11 Compress...

Page 19: ...y period 12 HOLDY_13 Holiday period 13 HOLDY_14 Holiday period 14 HOLDY_15 Holiday period 15 HOLDY_16 Holiday period 16 5 14 Option 156 energy management option This option requires the installation o...

Page 20: ...building management system or the programmable controllers to communicate with the Touch Pilot interface It is activated if the optional BACnet activation key dongle is present on the electronic contr...

Page 21: ...circuit has been shut down due to a fault The Reset alarms menu on the main interface displays up to five fault codes that are active on the unit 7 3 Resetting alarms When the cause of the alarm has...

Page 22: ...rd 1 Automatic if the communi cation is re established Unit shuts down Bus installation fault or defective slave board 23 4501 Communication loss with auxiliary board 1 As above Unit continues to oper...

Page 23: ...r pump connection 63 10074 Fault condenser pump 2 Manual Unit shuts down Pump overheats or poor pump connection 64 10078 High discharge gas temperature circuit A Manual Circuit A shuts down Defective...

Page 24: ...ontact Carrier Service 95 Alarm Torque loss Contact Carrier Service 243 Alarm IGBT defective Contact Carrier Service 251 Critical alarm New parts detached Contact Carrier Service 301 Alarm Problem in...

Page 25: ...ert Curve end Contact Carrier Service 95 Alert Torque loss Contact Carrier Service 96 Alert Start up delayed Contact Carrier Service 97 Alert Stop delayed Contact Carrier Service 98 Alert Clock proble...

Page 26: ......

Page 27: ......

Page 28: ...om www certiflash com Order No 13475 12 2016 Supersedes order No 13475 07 2016 Manufactured for CARRIER in France The manufacturer reserves the right to change the specification without prior notice P...

Reviews: