Associated table: 

PUMPSTAT - Pump status

No.

Status

Unit

Displayed text*

Description

1

yes/no

-

Cooler Flow Setpoint Out

Evaporator fl ow setpoint output

2

on/off 

-

Cooler Pump #1 Command

Evaporator pump control 1

3

on/off 

-

Cooler Pump #2 Command

Evaporator pump control 2

4

on/off 

-

Rotate Cooler Pumps ?

Evaporator pump rotation?

5

open/closed

-

Cooler Flow Switch

Flow switch

6

on/off 

-

Condenser Pump Command1

Condenser pump control 1

7

on/off 

-

Condenser Pump Command2

Condenser pump control 2

8

on/off 

-

Rotate Condenser Pumps ?

Condenser pump rotation?

9

open/closed

-

Condenser Flow Status

Condenser fl ow status

       

Associated table: RUNTIME - 

Run times

No.

Status

Unit

Displayed text*

Description

1

-

hour

Machine Operating Hours

Unit operating hours

2

-

-

Machine Starts Number

Number of unit starts

3

-

hour

Compressor A Hours

Operating hours, compressor A

4

-

-

Compressor A Starts

Number of starts, compressor A

5

-

hour

Compressor B Hours

Operating hours, compressor B

6

-

-

Compressor B Starts

Number of starts, compressor B

7

-

hour

Cooler Pump #1 Hours

Operating hours, evaporator pump 1

8

-

hour

Cooler Pump #2 Hours

Operating hours, evaporator pump 2

9

-

hour

Condenser Pump #1 Hours

Operating hours, condenser pump 1

10

-

hour

Condenser Pump #2 Hours

Operating hours, condenser pump 2

       

Associated table: MODES - Modes

No.

Status

Unit

Displayed text*

Description

1

yes/no

-

Start-up delay in eff ect

Start-up delay in eff ect

2

yes/no

-

Second Setpoint in Use

Second setpoint in use

3

yes/no

-

Reset in eff ect

Setpoint reset active

4

yes/no

-

Demand limit active

Demand limit active

5

yes/no

-

Cooler Pump Rotation

Evaporator pump rotation

6

yes/no

-

Pump Periodic Start

Periodic pump start-up

7

yes/no

-

Night Low Noise Active

Night mode active

8

yes/no

-

Master Slave Active

Master/slave active

9

yes/no

-

Auto Changeover Active

Automatic changeover active

10

yes/no

-

Condenser Pump Rotation

Condenser pump rotation

11

yes/no

-

Cond Pump Periodic Start

Periodic condenser pump start-up

12

yes/no

-

Ice Mode in Eff ect

Ice storage mode active

       

Associated table: SETPOINT - Setpoint table

No.

Status

Default

Unit

Displayed text*

Description

1

-28.9 to 26.0

6.7

°C

Cooling Setpoint 1

Cooling setpoint 1

2

-28.9 to 26.0

6.7

°C

Cooling Setpoint 2

Cooling setpoint 2

3

-28.9 to 26.0

6.7

°C

Cooling Ice Setpoint

Ice storage setpoint

4

0.1 to 11.1

0.6

^C

Cooling Ramp Loading

Cooling ramp loading

5

26.7 to 63.0

37.8

°C

Heating Setpoint 1

Heating setpoint 1

6

26.7 to 63.0

37.8

°C

Heating Setpoint 2

Heating setpoint 2

7

0.1 to 11.1

0.6

^C

Heating Ramp Loading

Heating ramp loading

8

3.9 to 50.0

23.9

°C

Cool Changeover Setpt

Auto changeover setpoint, cooling

9

0 to 46.1

17.8

°C

Heat Changeover Setpt

Auto changeover setpoint, heating

10

26.7 to 48.9

35.0

°C

Water Val Condensing Stp

Water valve condensing setpoint

11

0 to 100

100

%

Switch Limit Setpoint 1

Limit setpoint switch 1

12

0 to 100

100

%

Switch Limit Setpoint 2

Limit setpoint switch 2

13

0 to 100

100

%

Switch Limit Setpoint 3

Limit setpoint switch 3

Depends on selected language, default is English

No.

Status

Unit

Displayed text*

Description

22

on/off 

-

Drycooler Fan 6

Output, dry cooler 6

23

on/off 

-

Drycooler Fan 7

Output, dry cooler 7

24

on/off 

-

Drycooler Fan 8

Output, dry  cooler 8

25

0 to 10

V

Dry Cool Vfan 1 Output

Dry Cooler variable speed fan 1 output

26

0 to 10

V

Dry Cool Vfan 2 Output 

Dry Cooler variable speed fan 2 output

Summary of Contents for Touch Pilot 30XW-V

Page 1: ...CONTROLS MANUAL Touch Pilot Control 30XW V 30XWHV 30XW V ZE Original document AquaForce PUREtec with R 1234ze E...

Page 2: ...tch 17 5 6 Heating cooling selection 17 5 7 Control point 17 5 8 Capacity limitation 18 5 9 Night mode 18 5 10 Capacity control 18 5 11 Compressor short cycling protection 18 5 12 Option 152 saturated...

Page 3: ...2 1 General Touch Pilot is a system for controlling 30XW V 30XWHV single circuit or dual circuit water cooled units with R 134a refrigerant as well as 30XW V ZE single circuit or dual circuit water c...

Page 4: ...lure The green LED flashes continuously on all boards to show that the board is communicating correctly over its internal bus If the LED is not flashing this indicates a LEN bus wiring problem When th...

Page 5: ...flow setpoint of the water flow switch 3 6 Frequency variator The frequency variator is used to control the compressor It allows compressor start up and capacity control by modify ing the supply freq...

Page 6: ...s allows control of the unit occupancy occupied unoccupied Contact 3bis capacity limit selection 2 J4 Ch09 73A 74A NRCP2 BASE EMM A3 energy management This contact is only available with the energy ma...

Page 7: ...l features 4 3 1 Buttons Unit is running or in standby Unit is off Home Access to menus Not logged in Logged in No alarm Alert Alarm Back Previous page Next page More information Click this button Val...

Page 8: ...rce level is lower than the equipment controller s level 4 4 On off screen 4 4 1 Unit start up With the unit in Local Off mode press to display the list of operating modes Select the required mode Sho...

Page 9: ...n a forceable point of a data screen 4 10 Time schedule screen Forced Auto Forced value The auto button cancels a forced point 1 Selection of the applicable days for the time schedule 2 Modification o...

Page 10: ...7 0 to 2 Heat cool select Heating cooling selection via CCN or BACnet IP option 8 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 9 0 to 2 Setpoint select Setpoint selection via CCN or BACnet IP option 10...

Page 11: ...te On Off Switch Remote On Off Switch 2 open closed Remote HeatCool Switch Heating cooling selection switch 3 open closed Remote Setpoint Switch Setpoint selection switch 4 open closed Limit Switch 1...

Page 12: ...tion Evaporator pump rotation 6 yes no Pump Periodic Start Periodic pump start up 7 yes no Night Low Noise Active Night mode active 8 yes no Master Slave Active Master slave active 9 yes no Auto Chang...

Page 13: ...trol 11 00 00 0 Night Mode Start Hour Night mode start hour 12 00 00 0 Night Mode End Hour Night mode end hour 13 100 Night capacity Limit Night mode capacity limit 14 yes no no Current Limit select A...

Page 14: ...Full Reset Value Outdoor temperature max reset 21 0 to 13 9 0 C Delta T No Reset Value Delta T no reset 22 0 to 13 9 0 C Delta T Full Reset Value Delta T max reset 23 0 to 20 0 mA Current No Reset Val...

Page 15: ...Alarm 5 Current JBus alarm 5 4 13 3 BROCASTS menu Broadcast menu Name Format Value Description Ccnbroad 0 1 2 2 Activates broadcast 0 deactivated 1 broadcast time holidays on the network 2 broadcast t...

Page 16: ...start up is 1 minute configurable between 1 and 15 minutes the pump will run for at least one minute before the first compressor starts The pump is kept running for 20 seconds after the unit goes to...

Page 17: ...ling selection For units configured in the heat pump mode heating cooling selection can be controlled in various ways depending on the active operating type locally at the unit using the HC_SEL item i...

Page 18: ...ading functions can also affect the temperature control accuracy Compressors are started in a sequence designed to equalise the number of start ups value weighted by their operating time 5 11 Compress...

Page 19: ...y period 12 HOLDY_13 Holiday period 13 HOLDY_14 Holiday period 14 HOLDY_15 Holiday period 15 HOLDY_16 Holiday period 16 5 14 Option 156 energy management option This option requires the installation o...

Page 20: ...building management system or the programmable controllers to communicate with the Touch Pilot interface It is activated if the optional BACnet activation key dongle is present on the electronic contr...

Page 21: ...circuit has been shut down due to a fault The Reset alarms menu on the main interface displays up to five fault codes that are active on the unit 7 3 Resetting alarms When the cause of the alarm has...

Page 22: ...rd 1 Automatic if the communi cation is re established Unit shuts down Bus installation fault or defective slave board 23 4501 Communication loss with auxiliary board 1 As above Unit continues to oper...

Page 23: ...r pump connection 63 10074 Fault condenser pump 2 Manual Unit shuts down Pump overheats or poor pump connection 64 10078 High discharge gas temperature circuit A Manual Circuit A shuts down Defective...

Page 24: ...ontact Carrier Service 95 Alarm Torque loss Contact Carrier Service 243 Alarm IGBT defective Contact Carrier Service 251 Critical alarm New parts detached Contact Carrier Service 301 Alarm Problem in...

Page 25: ...ert Curve end Contact Carrier Service 95 Alert Torque loss Contact Carrier Service 96 Alert Start up delayed Contact Carrier Service 97 Alert Stop delayed Contact Carrier Service 98 Alert Clock proble...

Page 26: ......

Page 27: ......

Page 28: ...om www certiflash com Order No 13475 12 2016 Supersedes order No 13475 07 2016 Manufactured for CARRIER in France The manufacturer reserves the right to change the specification without prior notice P...

Reviews: